Baseline Systems BaseStation 6000 User Manual

Page 32

Advertising
background image

BaseStation 6000 Site Controller Manual

24 |

P a g e

To perform the manual calibration, saturate the soil around the sensor by pouring approximately two gallons of water directly

over the spot where the sensor is buried. Over the next several hours, the water will spread out through capillary movement. As

a rule, it is best to wait 24 hours to get an accurate field capacity reading. Test the biSensor to get the moisture percentage

reading, and then set the upper moisture level (upper threshold) at or slightly below this moisture reading. Refer to Testing

Sensors on page 100.

The most common method for manually calibrating a sensor for the lower moisture level (lower threshold) is to let the

landscape dry out to the point where watering is desired and then test the biSensor again to get the moisture percentage

reading and use that reading as the lower moisture level (lower threshold).

For more information, refer to Adjusting Programming with biSensors on page 41, and refer to the Graphs section on page 92

for information about reading and interpreting the soil moisture graphs. When the graph displays, you have many different

tools for changing how the graph looks. Refer to Adjusting the Data View on a Graph on page 93 for details.

To set the upper and lower moisture levels for a biSensor that is associated with an auto zone

1. Click the Adjust Zone

(1)

tab on the Main Page.

2. Click the Graph

(2)

button for the auto zone that you want to set the moisture

levels for. The Automatic Zone and Sensor Management window opens.
Note: When you adjust the auto zone, the new settings will be applied to all zones

that are linked to it.

3. If you are using Water Strategy 1 or 2, use the slider

(3)

on

the right side of the graph to set the Upper Moisture Level

represented by the green line. The Upper Moisture Level

refers to the field capacity of the soil. Set the Upper

Moisture Level at or slightly below the biSensor reading

that you took after allowing the water to soak in around

the sensor for 24 hours.

4. If you are using Water Strategy 2 or 3, you can adjust the

Lower Moisture Level with the slider

(4)

on the left of the

graph. The Lower Moisture Level is represented by the red

line. This setting represents how dry you will let the soil

become before watering again.

5. Click Return

(5)

to close the window.

Continuous Calibration – The Auto Calibration option on the Automatic Zone and Sensor Management window enables the

controller to continuously measure the field capacity of the soil. When you enable auto calibration, the controller applies water

to the auto zone (the zone where the sensor is buried) during every run cycle until the response curve slows. After the

controller has measured field capacity, it is able to use this data to set an upper or lower threshold based on this reading. You

can then choose to use this threshold or reset it as needed.

If you have your thresholds precisely set, you can use continuous calibration to make minor adjustments that will improve plant

health. Keep the following points in mind:

WARNING! Continuous calibration uses a lot of water while attempting to determine field capacity especially if the sensor is

placed in a very dry area.

• If you enable continuous calibration when the soil moisture content is already high, the calibration will fail because the

system must be able to detect a change in soil moisture content.

Advertising