7. In the Pipe Fill Time

(3)

field, type the number of seconds that it takes to fill the empty line, activate the valve, and reach a

steady state operating pressure.
Note: The easiest way to determine the pipe fill time is to turn on the zone, and then time how long it takes for you to see

water flowing at a steady pressure.

8. In the Turn Off Time field, type the number of seconds required for the longest valve on the program to completely close

after power is no longer applied to the solenoid.
Note: The Turn Off time allows your system to turn off the previous zone and stabilize after the last zone so that the flow

from the previous zone is not included in the current zone’s learn-flow cycle.

9. To start the Learn Flow process, click Test

(4)

. If you selected the Learn Flow Now option, the test starts immediately. If you

selected Learn Flow at Time, the process will begin at the specified time. The status of the Learn Flow process displays in

the field

(5)

at the bottom of the Learn Flow By Program group box and a colored rectangle shows the actual stage of the

process. A cyan colored rectangle means that the process is starting or transitioning to a different zone. A dark-blue

rectangle means that flow learning is occurring.

10. You can also learn flow for one zone by using the fields in the Learn One Zone group box

(6)

. Type the Remote Base Unit

and the Zone Address Number that you want to learn, and then press Test

(7)

. The system uses the program number, pipe

fill time, and turn off time, that you entered in the Learn Flow By Program group box.

Note: The results of the Learn Flow process are displayed in the pane

(8)

on the right of the Learn Flow tab. The results also

display in the Report Viewer. The report is saved in a file in the Learn Flow folder under the folder structure for the BaseStation

6000 software on your computer’s hard drive. When the Learn Flow process has completed, the results are automatically

recorded in the appropriate fields on the Config Zone tab on the Main Page.