Operational testing, Installation – Baseline Systems BHM Series Hydrometer User Manual

Page 16

Advertising
background image

16

Hydrometers Operation and Maintenance Manual

Operational Testing

INSTALLATION

Before the hydrometer is placed into service, you should perform the following tests to verify that

it is operating properly:

A. To test water flow and manual operation:

• Set 3-Way Selector to the “Open position”.

• Turn on the water flow to the hydrometer.

• Visually verify that water is flowing downstream from the hydrometer in appropriate

quantities.

• Verify that the leak detector, pointers and the totalizer are functioning properly.

• Check all hoses, connections, pilot valves, etc. for leakage and repair as necessary.

• Set 3-Way Selector to the “Close position”.

• Verify that the water flow downstream has stopped.

B. To test automatic and remote operation:

• Set 3-Way Selector to the “Auto” position.

• Turn on the water flow to hydrometer.

• Verify that the hydrometer output is correctly received by the controller or control center.

• Use the controller or control center to close the hydrometer. Verify that the water flow

downstream has stopped.

• Use the controller software to test operation of the hydrometer under various applications

and conditions such as pressure reducing, pressure sustaining and flow regulation.

• Your hydrometer is now ready for routine use.