Setup Related Digital Joins (continued)

Signal Name

Symbol

I/O

Definition

DUAL_FUEL_HP_F

Advanced Output Asserted when dual-fuel heat pump system declared,

In conventional heat pump systems, aux heat may be
used to supplement heat pump heat. In dual-fuel
setups, the aux heat output runs in place of the heat
pump in cold weather. Requires outdoor temperature
sensor.

RADIANT_F

Advanced

Output

Asserted when a heat/cool system is declared as
Radiant, Radiant systems require slightly different
control characteristics than forced air systems

FAN_IN_HEAT_F

Advanced Output Asserted when “Run Fan in Heat” is “yes”, Most

heating systems control the fan if it is needed, but
some systems may require the fan to be controlled by
the thermostat

HEAT_1_STG_F

Advanced

Output

Asserted when one stage of heat is defined

HEAT_2_STG_F

Advanced

Output

Asserted when two stages of heat are defined

COOL_1_STG_F

Advanced

Output

Asserted when one stage of cooling is defined

COOL_2_STG_F

Advanced

Output

Asserted when two stages of cooling are defined

TEMP_IN_F

Advanced

Output

Asserted when Fahrenheit units are used

TEMP_IN_C

Advanced

Output

Asserted when Celsius units are used

DISP_FP_HUM_F

Advanced

Output

Asserted when front panel object is set to be humidity

DISP_FP_OD_F

Advanced Output Asserted when front panel object is outdoor

temperature

DISP_HUM_F

Advanced

Output

Asserted when humidity pages are enabled

DISP_GLOBAL_F

Advanced

Output

Asserted when global update page is enabled

DISP_OUTDOOR_F

Advanced

Output

Asserted when outdoor page is enabled

DISP_REM_BUTTONS1_F

Advanced

Output

Asserted when remote button page 1 is enabled

DISP_REM_BUTTONS2_F

Advanced

Output

Asserted when remote button page 2 is enabled

DUAL_SP_AUTO_MODE_F

Advanced Output Asserted when using 2 point auto mode, unasserted

means using single point auto mode

LOW_TEMP_HUM_COMP_F

Advanced

Output

Asserted when low temperature humidity compensation
is enabled, helps prevent condensation on windows in
cold weather

Sensor Setup Related Digital Joins

Signal Name

Symbol

I/O

Definition

USE_LOC_TEMP_F

Advanced

Output

Asserted when using built in temperature sensor

USE_R1_TEMP_F

Advanced

Output

Asserted when using remote 1 temperature sensor

USE_R2_TEMP_F

Advanced

Output

Asserted when using remote 2 temperature sensor

OMIT_LOC_TEMP_F

Advanced

Output

Asserted when Omitting built in temperature sensor

OMIT_R1_TEMP_F

Advanced

Output

Asserted when Omitting remote 1 temperature sensor

OMIT_R2_TEMP_F

Advanced

Output

Asserted when Omitting remote 2 temperature sensor

R1_T_OUTDOOR_F

Advanced Output Asserted when remote 1 temperature sensor has been

declared as outdoor (OD)

R2_T_OUTDOOR_F

Advanced

Output

Asserted when remote 2 temperature sensor has been
declared as outdoor (OD)

USE_LOC_HUM_F

Advanced Output Asserted when using built in humidity sensor

(THSTAT)

USE_R1_HUM_F

Advanced

Output

Asserted when using remote 1 humidity sensor