Problem solving, Troubleshooting, Thermostats crestron chv-tstat and chv-thstat – Crestron electronic CHV-TSTAT User Manual

Page 42

Advertising
background image

Thermostats Crestron

CHV-TSTAT and CHV-THSTAT

Problem Solving

Troubleshooting

The table below provides corrective action for possible trouble situations. If further
assistance is required, please contact a Crestron customer service representative.

CHV-TSTAT/CHV-THSTAT Troubleshooting

TROUBLE

POSSIBLE

CAUSE(S)

CORRECTIVE ACTION

No power from
system

Check for +24V on pins 24(C)
and 24(R)

No display

Incorrect mounting
to backplate

Check thermostat mounting

No power to
thermostat

Check circuit breaker
Check 24V connection at
thermostat and at furnace/air
conditioner
Recheck wiring connections

Heating/Cooling
system not
operating*

Thermostat
minimum off times
operating both
systems

Wait 5 minutes and/or consult
HVAC contractor

Indicator displays
Heat On, but no
heat from register

Fan turns on when
furnace reaches
setpoint

Cannot change
temperature
setting

The upper or lower
temperature limits
were reached

Wait five minutes, and then
recheck registers.
Setpoint heat range is 38 – 90º F
(3-38º C).
Setpoint cool range is 59-100º F
(15 – 38º C)

Furnace cycles too
quickly

Anticipator setting
too high

Reprogram anticipator. Refer to
“Thermostat Setup” on page 17

High temperature
variance

Anticipator setting
too low

Reprogram anticipator. Refer to
“Thermostat Setup” on page 17

Displays “Sensor
Error” and
thermostat is
locked-up

All temperature
sensors are disabled
or have failed

Remove the thermostat from the
backplate and reinsert while
simultaneously pressing and
holding the

MODE and DOWN

buttons to return to Setup Mode

Displays
“NetDown”

No Crestron
program or the
program does not
have a device at this
net address included
in this system

Fix program, if one is needed

Cannot leave
setup

Sensor configuration
not valid

Ensure sensor setup meets
system requirements
Refer to Sensor Setup screen

*H1, H2, C1, C2 may appear but the system will not activate until the 5 minute timer guards

have been satisfied.

38

Thermostats: CHV-TSTAT and CHV-THSTAT

Operations and Installation Guide – DOC. 8163B