Baumer N 150 User Manual

Page 13

Advertising
background image

N 150

www.baumer.com

13

Resolution
This parameter defines the resolution of the actual value. Upon altering the resolution the decimal point is shifted
correspondingly by one digit to the right or left, same applies also to actual value and target. The target values
however are not converted correspondingly but only the decimal point is shifted. When editing the machine please
pay attention to defining the resolution first so that the target values are transmitted to the SPAs with the
corresponding resolution.

0

Resolution 1/100 mm resp. 1/1000 inch visualized in the display: 000.00 mm resp. 00.000 inch

1

Resolution 1/10 mm resp. 1/100 inch visualized in the display: 0000.0 mm resp. 000.00 inch


4.3.2. Read /write tolerance compensation and tolerance window, „b“ (62h)

This command is utilized to read or write the parameters tolerance compensation and tolerance window.

Example 1: Read parameter (tolerance compensation = 0.15; tolerance window = 0.25)

SOH

Adr

Cmd

EOT

CRC

Transmission

01h

20h

62h

04h

48h

SOH

Adr

Cmd Tolerance compensation=0.15

Tolerance window=0.25

EOT

CRC

Response

01h

20h

62h

30h

30h

31h

35h

30h

30h

32h

35h

04h

AAh



Example 2: Write parameter (tolerance compensation = 1.30; tolerance window = 5.00)

SOH

Adr

Cmd Tolerance compensation =1.30

Tolerance window r=5.00

EOT

CRC

Transmission

01h

20h

62h

30h

31h

33h

30h

30h

35h

30h

30h

04h

20h

SOH

Adr

Cmd Tolerance compensation =1.30

Tolerance window r=5.00

EOT

CRC

Response

01h

20h

62h

30h

31h

33h

30h

30h

35h

30h

30h

04h

20h


4.3.3. Read / write spindle pitch (scaling factor) „c“ (63h)

This command is utilized to read or write the scaling factor of the spindle pitch within the range from
0,0000001...9,9999999. The decimal point is not transmitted.

How to calculate the scaling factor:

Resolution per turn: 14,40 mm

Spindle pitch:

4,00 mm

pitch 4,00
Scaling factor = ──────────── = ───── = 0,2777777

Resolution per turn 14,40

Example 1: Read scaling factor (scaling = 1.000000)

SOH

Adr

Cmd

EOT

CRC

Transmission

01h

20h

63h

04h

4Ah

SOH

Adr

Cmd

scaling = 1.0000000

EOT

CRC

Response

01h

20h

63h

31h

30h

30h

30h

30h

30h

30h

30h

04h

4B


Example 2: Write scaling factor (scaling = 0.2777777)

SOH

Adr

Cmd

scaling = 0.2777777

EOT

CRC

Transmission

01h

20h

63h

30h

32h

37h

37h

37h

37h

37h

37h

04h

30h

SOH

Adr

Cmd

scaling = 0.2777777

EOT

CRC

Response

01h

20h

63h

30h

32h

37h

37h

37h

37h

37h

37h

04h

30h