Installation

|

NOTE:

For Europe, the emergency switch requirements are detailed in Harmonized document HD-384-48 S1,

“Electrical Installation of the Buildings, Part 4: Protection for Safety, Chapter 46: Isolation and Switching.”

REPO Connections

Wire Function

Terminal Wire Size Rating

Suggested Wire Size

REPO

4–0.32 mm

2

(12–22 AWG)

0.82 mm

2

(18 AWG)

NOTE:

The pins must be open to keep the UPS running. If the UPS shuts down because the REPO connector

pins are shorted, restart the UPS by re-opening the REPO connector pins and turning on the UPS manually.
Maximum resistance in the shorted loop is 10 ohm.

NOTE:

Always test the REPO function before applying your critical load to avoid accidental load loss.

NOTE: Remove

jumper if installed

Figure 18. REPO Connector

To install the REPO switch:

1

Verify that the UPS is off and disconnected from utility power.

2

Remove the REPO connectors from the accessory box.

NOTE:

Verify that there is no jumper installed in the REPO connector. If a jumper is installed, remove it before

connecting to the REPO port. See Figure 18.

3

Connect the REPO connector to the REPO port labeled IN on the UPS rear panel.

CAUTION:

If you are daisy-chaining the REPO function, observe the following connection requirements to

avoid unintentional shutdown of the UPS:

S

The left pin of the REPO port labeled OUT on the first UPS must be connected to the left pin of the REPO port
labeled IN on the second UPS.

S

The right pin of the REPO port labeled OUT on the first UPS must be connected to the right pin of the REPO
port labeled IN on the second UPS.