Dell UPS 10000R User Manual

Page 82

Advertising
background image

82

|

Specifications

Table 16. Battery

Configuration

10 kW: (24) 288V, 9.0 Ah internal batteries; EBM: (24) 288V, 9.0 Ah

Battery Type

YUASA NPW 45-12 9.0 Ah

Voltage

10 kW: 288 Vdc internal; EBM : 288 Vdc/40A

Fuses

UPS: (1) 80A fuses

EBM: (1) 80A fuses

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

Charging

10 kW internal batteries: Approximately 4 hours to 90% usable capacity at nominal

line and no supplementary power supply load

EBM: Approximately 8 hours to 90% usable capacity at nominal line and no

supplementary power supply load

Monitoring

Advanced monitoring for earlier failure detection and warning

Battery Runtimes*

10 kW internal batteries: 5 minutes at full load/14 minutes at half load

10 kW with one EBM attached: 13 minutes at full load/35 minutes at half load

* Battery runtimes are approximate and vary depending on the load configuration and battery charge.