Operation

|

Table 7. Settings (continued)

Description

Default Setting

Available Settings

Set Date and Time

Set Month, Day, Year, Hours, Minutes, and Seconds
Date: mm/dd/yyyy
Time: hh:mm:ss

NOTE:

The date format is dependent on the

language selection.

NOTE:

Time is a 24-hour clock.

01/01/2012
12:00:00

Control Commands from Serial

Port

[Enabled] [Disabled]
If Enabled, control commands are accepted through

the serial port, USB ports, or option card.
If Disabled, configuration and load control

commands are restricted to LCD only.

Enabled

Output Voltage

[208V] [230V] [Auto-sensing]

NOTE:

Numerical output voltage settings that are

configured in Standby mode take effect

immediately. Auto sensing and any settings that are

configured outside of Standby mode take effect

after the next power off and restart. Selecting auto

sensing disables the battery start feature until after

the next successful startup on utility power.

Auto-sensing

NOTE:

The default

auto sensing runs

once to set the

output voltage and

then is disabled.

Output Frequency

[50Hz] [60Hz] [Auto-sensing]

NOTE:

Numerical output voltage settings that are

configured in Standby mode take effect

immediately. Auto sensing and any settings that are

configured outside of Standby mode take effect

after the next power off and restart. Selecting auto

sensing disables the battery start feature until after

the next successful startup on utility power.

Auto-sensing

NOTE:

The default

auto sensing runs

once to set the

output voltage and

then is disabled.

Overload Alarm Level

[10%] [20%] [30%]...[100%]
If 100%, the UPS issues an Output Overload alarm

at load > 100%.

NOTE:

Output Overload Level 1 by default is set to

100% and is configurable from 10% to 100% in 10%

increments through the LCD setting menu. This

feature allows customers to be alerted before the

UPS has reached its rated capacity limits.

100%

Power strategy

[Normal] [High Efficiency] [Converter]
See “Setting the Power Strategy” on page 54.

Normal