Dell UPS 10000R User Manual

Page 50

Advertising
background image

50

|

Operation

Table 7. Settings (continued)

Description

Default Setting

Available Settings

Automatic Start Delay

[Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 57.

0s: Load Segment 1

(LS1)
1s: Load Segment 2

(LS2)

Automatic on Battery Shutdown

[Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 57.

Off

Start on Battery

[Enabled] [Disabled]

NOTE:

Battery start is disabled from the factory and

remains disabled until the UPS has been powered

from utility and enters Standby mode. After the

UPS has been started once from utility, the Start on

Battery feature is automatically enabled. If this is set

by the user, it remains set.

Enabled

Battery Saving Mode

[Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the

UPS is on battery and output power is below the

selected level.

Disabled

On Battery Notice Delay

[0s] [1s] [2s]...[99s]
The UPS issues a “UPS on battery” notice in the

specified number of seconds after the UPS starts to

discharge the batteries.

0s

Site Wiring Fault Alarm

[Enabled] [Disabled]

Disabled

Bypass Voltage Low Limit

[-6%] [-7%]...[-20%] of nominal
The Bypass operation is disabled if the measured

bypass voltage level is below the nominal output

voltage (-15%).

NOTE:

The Qualify Bypass setting may overrule the

Bypass Voltage Low Limit setting.

-15% of nominal

Bypass Voltage High Limit

[+6%] [+7%]...[+20%] of nominal
The Bypass operation is disabled if the measured

bypass voltage level is above the nominal output

voltage (+10%).

NOTE:

The Qualify Bypass setting may overrule the

Bypass Voltage High Limit setting.

+10% of nominal