55

Operation

|

Table 8. UPS Behavior in Converter Mode

Load

Output
Frequency
Setting

Input Frequency
(Hz)

Output
Frequency
(Hz)

UPS Behavior

≤50%

50 Hz

47–53

47–53

UPS in Converter mode synchronizes the output

frequency with the input frequency.

45–46 or 54–65

50

UPS in Converter mode converts the input

frequency to 50 Hz output frequency

<45 or >65

50

UPS transfers to Battery mode to provide 50 Hz

output frequency.

60 Hz

57–63

57–63

UPS in Converter mode synchronizes the output

frequency with the input frequency.

45–56 or 64–65

50

UPS in Converter mode converts the input

frequency to 60 Hz output frequency.

<45 or >65

50

UPS transfers to Battery mode to provide 60 Hz

output frequency.

> 50%

50 Hz

47–53

47–53

UPS in Converter mode synchronizes the output

frequency with the input frequency.

45–46 or 54 -55

50

UPS in Converter mode converts the input

frequency to 50 Hz output frequency.

<45 or >55

50

UPS transfers to Battery mode to provide 50 Hz

output frequency.

60 Hz

57–63

57–63

UPS in Converter mode synchronizes the output

frequency with the input frequency.

55–56 or 64–65

50

UPS in Converter mode converts the input

frequency to 60 Hz output frequency.

<55 or >65

50

UPS transfers to Battery mode to provide 60 Hz

output frequency.