Dell UPS 10000R User Manual

Page 51

Advertising
background image

51

Operation

|

Table 7. Settings (continued)

Description

Default Setting

Available Settings

Qualify Bypass

[Always] [Never] [Bypass Disabled]
If Always, Bypass operation is allowed when:

S Bypass voltages > the value set for Bypass

Voltage Low Limit

S Bypass voltages < the value set for Bypass

Voltage High Limit

S Bypass frequency > (nominal frequency -3 Hz)
S Bypass frequency < (nominal frequency +3 Hz)
S Inverter is synchronized with Bypass when

unsynchronized transfers are disabled by the

value set for Unsynchronized Transfers

If Never, Bypass operation is always allowed; voltage

and frequency limits are not in use.
If Bypass Disabled, Bypass operation is prohibited.

Always

Synchronization Window

[Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±1.5 Hz]

[±2.0 Hz] [±2.5 Hz] [±3.0 Hz]
If ±3.0 Hz, on inverter operation the inverter tries to

synchronize with the Bypass when the Bypass

frequency is not more than 3 Hz from the nominal

output frequency; otherwise, the inverter goes to

nominal frequency. On Bypass mode, the sync

window is always ±3 Hz.

NOTE:

In Sync Disabled state, if the Bypass

operation is allowed, the UPS synchronizes only

when it is operating on Bypass mode.

±

3.0 Hz

Unsynchronized Transfers

[Enabled] [Disabled]
If Enabled, unsynchronized transfers to the Bypass

are allowed.
If Disabled, unsynchronized transfers to the Bypass

are not allowed.

NOTE:

The Qualify Bypass setting may overrule the

Unsynchronized Transfers setting.

Enabled

External Battery Modules (EBMs)

[0] [1]
See “Configuring the UPS for an EBM” on page 60.

0