Title: Engineering Product Specification Telecom Circuit Protector

Revision: L

Printed on: 7/14/2003

Sheet

6

of

18

This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design
applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of
any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a
product has been selected, it should be tested by the user in all possible applications.

4.2.4 Orthogonal View






5. ELECTRICAL SPECIFICATIONS


5.1 Voltage Rating

Catalog Symbol

Voltage Rating

AC

TCP500mA

250 V

TCP1.25A

250 V

TCP2A

250 V




5.2 Interrupting Rating


5.2.1

AC Interrupting Rating (Measured at designated voltage, 100% power factor)

Catalog Symbol

250 V

600 V*

TCP500mA

50 A

40A

TCP1.25A

50 A

60 A

TCP2A

50 A

60 A

A C

Interrupting Rating


*600V, 60A Interrupting ratings test were performed by closing the circuit between 50

°

and 70

°

on the voltage wave.