Title: Engineering Product Specification Telecom Circuit Protector

Revision: L

Printed on: 7/14/2003

Sheet

7

of

18

This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design
applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of
any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a
product has been selected, it should be tested by the user in all possible applications.

5.3 Time vs. Current Characteristic

(Measured with a Kepco constant current power supply)


5.3.1 For TCP500mA and TCP1.25A

% of Amp Rating

Opening Time

100%

4 Hours Minimum

250%

1 Second Minimum

250%

4 -10 Seconds Typical

250%

120 Seconds Maximum

300%*

10 Seconds Maximum

*If the device does not open at 250% within 120 seconds, increase current to 300% of amp rating.

Device must open in 10 seconds maximum.



5.3.2 For TCP2A

Current Level

Opening Time

2.2A**

30 minutes minimum

7A

opens before Bussmann MDL-2

25A

opens before Bussmann MDL-2

40A

opens before Bussmann MDL-2

% of A mp Rating

Opening Time

100%

4 Hours M inimum

250%

1 Second M inimum

250%

4 -10 Seconds Typical

250%

120 Seconds M aximum

300%*

10 Seconds M aximum


*If the device does not open at 250% within 120 seconds, increase current to 300% of amp rating.

Device must open in 10 seconds maximum.


** The TCP2A may have a maximum temperature rise of 100

°C after carrying 2.2A for thirty minutes.



5.4 DC Cold Resistance

(Measured at 10% of rated current)

Catalog Symbol

Resistance (ohms)

Min.

Typ.

Max.

TCP500mA

0.420

0.530

0.640

TCP1.25A

0.107

0.128

0.150

TCP2A

0.050

0.075

0.100