Up and Down Buttons

To view the “High Temp” recorded by the
cooling unit, press the “Up” button once.

To view the “Low Temp” recorded by the
cooling unit, press the “Down” button once.

To reset the “High Temp” or “Low Temp”, press
the “Set” button for three seconds while “Hi”
or “Lo” is displayed. “RST” will blink three times
to indicate confirmation.

Set Button

The cooling unit is factory preset with a
Minimum Set Point of 58°F and a Temperature
Differential of 4°F. This means that the cooling
unit will turn on when the display rises above
62°F (58°F + 4°F), and turn off when the
display falls below 58°F. In this example, the
average temperature inside the cellar will be
60°F.

To view the Minimum Set Point, press the “Set”
button for one second.

To change the Minimum Set Point,

Press the “Set” button for three seconds
until °F” blinks

Press “Up” or “Down” button

Press “Set” button to confirm


The “Set” temperature will blink three times to
indicate confirmation

The recommended Minimum Set Point range
is 53 - 60°F. To change the Temperature
Differential, see “Advanced Operation” later
in this chapter.