Standard Protection Mechanisms

The cooling unit is programmed to shut down certain components to

protect those components, as well as the wine inside the cellar, under the

following circumstances:

Scenario

What it means

What happens

P1 Alarm

Probe 1, which senses the

temperature inside the

cellar and controls the

on/off cycles of the cooling

unit, has failed

The cooling unit enters a
timed auto-cycle mode
until Probe 1 is repaired or
replaced. In this mode, the
cooling unit will turn on for
12 minutes and off for 8
minutes.

Scenario

What it means

What happens

HA2 Alarm
P3 > 140° F

The condenser probe is
measuring temperatures
that are too hot

The compressor and
condenser fan will turn off
until the condenser
temperature falls below
120°F