2 profinet network connections, 3 led status indicators, Network status led (item 1) – Rice Lake 880 Performance Series Panel Mount Indicator/Controller - ProfiNet Interface Option Installation and Programming Manual User Manual
Page 11: Module status led (item 2)
Installation
7
2.2 ProfiNet Network Connections
Note
To configure an IP Address, refer to Section 4.1 on page 10.
2.3 LED Status Indicators
1
2
3
4
Figure 2-10. ProfiNet Module
Network Status LED (Item 1)
Table 2-1. Network Status LED
LED State
Description
Off
No power or connection with IP controller
Green, flashing
Connection with IP Controller established
I/O Controller in STOP state
Note
Note
A test sequence is performed on this LED during startup.
Module Status LED (Item 2)
Table 2-2. Module Status LED
LED State
Description
Off
Not Initialized No power - or - Module in SETUP or NW_INIT state
Green
Normal Operation Module has shifted from the NW_INIT state
Green, 1 flash
Diagnostic Event(s) Diagnostic event(s) present
Green, 2 flashes
Blink Used by engineering tools to identify the node on the
network
Red
Exception Error Module in state EXCEPTION
Red, 1 flash
Configuration Error Expected Identification differs from Real
Identification
Red, 2 flashes
IP Address Error IP address not set
Red, 3 flashes
Station Name Error Station Name not set
Red, 4 flashes
Internal Error Module has encountered a major internal error
A test sequence is performed on this LED during startup.