Acquire Tare (simulate TARE key press)

Command: 13, 0x00D
Parameter: Scale number

Command 13 acquires a tare based on the weight currently on the specified scale. The
indicator continues to return weight data in the current mode for the specified scale.

Clear Tare

Command: 14, 0x00E
Parameter: Scale number

Command 14 clears the tare for the specified scale. The indicator continues to return
weight data in the current mode for the specified scale.

Primary Units

Command: 16, 0x010
Parameter: Scale number

Command 16 switches the current format of the specified scale to the primary units
configured for that scale.

Secondary Units

Command: 17, 0x011
Parameter: Scale number

Command 17 switches the current format of the specified scale to the secondary units
configured for that scale.

Tertiary Units

Command: 18, 0x012
Parameter: Scale number

Command 18 switches the current format of the specified scale to the tertiary units
configured for that scale, if available.

Units Key Press (toggle units)

Command: 19, 0x013
Parameter: Scale number

Command 19 toggles between primary and secondary units of the specified scale.

Print Request

Command: 20, 0x014
Parameter: Scale number

Command 20 causes the indicator to execute a print command for the current scale.

Display Accumulator

Command: 21, 0x015
Parameter: Scale number

Command 21 causes the value of the accumulator for the specified scale to be
displayed and returned. This command is only valid if the accumulator for the
specified scale is enabled.

Clear Accumulator

Command: 22, 0x016
Parameter: Scale number

Command 22 clears the value of the accumulator for the specified scale. This
command is only valid if the accumulator for the specified scale is enabled.