Campbell Hausfeld CE7000 User Manual

Page 17

Advertising
background image

Series CE7000, CE8000 and CE9000

www.CH-Commercial.com

Troubleshooting Guide for Units in Service for a Period of Time

SyMptoM

CAuSe

Solution

Motor does not run

Loose electrical connections

The entire electrical system should be checked by a certified electrician�
The incoming wires and the compressor electrical connections should
be checked� Loose connections will cause malfunctions�

Blown fuse and / or tripped
breaker

The breaker and fuses required for this unit must be time delay�
A tripped breaker or blown fuse may result from a direct short to
ground, high current draw, improper wiring, incorrect fuse or breaker
size and/or type� This needs to be evaluated by a service center or
certified electrician�

Starter overload tripped

Check and reset if necessary� If the overload trips after the initial reset,
refer to the section of the manual that covers this issue�

Defective capacitor

Check and replace (if necessary) defective capacitor�

Defective magnetic starter

First check for any loose wiring and tighten if loose� Check and replace

(if necessary) defective magnetic starter�

Motor hums; motor

draws high amps, trips

overload, trips breaker,

or blows fuse on start up

Defective pressure switch

unloader

Drain the tank of all pressure. Restart compressor under no load. If

compressor is able to start, then the unloader needs to be checked�

If this problem is not corrected it will fail the motor and / or other

electrical components�

Defective check valve -

constant loss of tank

pressure

Determine if the check valve is working properly - pressure switch

unloader should quit hissing after the compressor shuts off� If the

hissing continues and if there is a constant loss of tank pressure, then

the check valve is not working properly� Replace check valve�

Loose electrical connections

The entire electrical system should be checked by a certified electrician�
The incoming wires and the compressor electrical connections should
be checked� Loose connections will cause malfunctions�

Defective capacitor

Check and replace (if necessary) defective capacitor�

Valve problem or blown

gasket

Check gasket and replace as needed� Other symptoms occur when a

valve is not sealing or a gasket is blown such as higher than normal amp

draw which may trip out the overload or breaker�

Compressor runs but

builds pressure slowly

Air leak

Check the entire system for leaks, including the compressor unit and
any piping attached to the compressor

Dirty air filter

Air filters need to be changed regularly based on usage and

environment� A dirty filter may appear to be clean� Change filters often�

Valve problem or blown

gasket

Check gasket and replace as needed� Other symptoms occur when a

valve is not sealing or a gasket is blown such as higher than normal amp

draw which may trip out the overload or breaker�

Tank cracked

Replace the tank� The unit should not be run under any conditions.

Tanks cannot be welded or patched�

Interstage safety valve

pops off when the unit is

running

Malfunctioning interstage

safety valve

Valve problem or blown gasket. High pressure air backflows into the

low pressure side of the pump� This is caused by valve leakage or blown

gasket�

Low head bolt torque

Check and retighten head bolts to specified torque�

Defective interstage safety

valve

Replace interstage safety valve� Under no circumstances plug the safety

valve port

Oil out breather

Worn rings or scored cylinder Replace rings and/or replace cylinder�
Compressor running hot

Make sure compressor is running the correct rotation� Compressor

should be clean and in a well ventilated area� Oil should be changed on

regular intervals according to the specifications listed in the manual�

Air filter must be changed as it gets dirty�

Continued on next page

17

Advertising
This manual is related to the following products: