Installation (continued) – Campbell Hausfeld CE7000 User Manual

Page 7

Advertising
background image

Series CE7000, CE8000 and CE9000

Installation (Continued)

pipinG

Never use plastic (PVC) pipe for compressed air.

Serious injury or death could result.

Any tube, pipe or hose connected to the unit must be able to
withstand the temperature generated and retain the pressure� All
pressurized components of the air system must have a pressure
rating of 200 psi or higher� Incorrect selection and installation
of any tube, pipe or hose could result in bursting and injury.
Connect piping system to tank using the same size fitting as the
discharge port�

inStAllinG A SHut-off vAlve
A shut-off valve should be installed on the discharge port of the
tank to control the air flow out of the tank� The valve should be
located between the tank and the piping system�

Never install a shut-off valve between the

compressor pump and the tank. Personal injury

and/or equipment damage may occur. Never use reducers in discharge
piping.

When creating a permanently installed system to distribute
compressed air, find the total length of the system and select
pipe size from the chart. Bury underground lines below the
frost line and avoid pockets where condensation can gather and
freeze�

Apply air pressure to the piping installation and make sure
all joints are free from leaks BEFORE underground lines are
covered. Before putting the compressor into service, find and
repair all leaks in the piping, fittings and connections�

WirinG (see page 8 for wiring diagrams)

All wiring and electrical connections must be

performed by a qualified electrician familiar

with induction motor controls. Installations must be in accordance
with local and national codes.

Overheating, short circuiting and fire damage

will result from inadequate wiring.

Wiring must be installed in accordance with National Electrical
Code and local codes and standards that have been set up
covering electrical apparatus and wiring� These should be
consulted and local ordinances observed. Be certain that
adequate wire sizes are used, and that:

1� Service is of adequate ampere rating�
2� The supply line has the same electrical characteristics

(voltage, cycles and phase) as the motor� Refer to motor
name plate for electrical ratings and specifications�

3� The line wire is the proper size and that no other equipment

is operated from the same line� The chart gives minimum
recommended wire sizes for compressor installations�

MiniMuM pipe Size for CoMpreSSed Air line

CfM

length of piping System

25 feet

50 feet

100 feet

250 feet

10

1/2 inch

1/2 inch

3/4 inch

3/4 inch

20

3/4 inch

3/4 inch

3/4 inch

1 inch

40

3/4 inch

1 inch

1 inch

1 inch

60

3/4 inch

1 inch

1 inch

1 inch

100

1 inch

1 inch

1 inch

1-1/4 inch

MiniMuM Wire Size (uSe 75°C Copper Wire)

Make sure voltage is correct with the motor wiring�
NOTE: If using 208 volts single phase, make sure the motor
name plate states it is rated for 208 volts single phase� 230 volt
single phase motors do not work on 208 volts unless they have
the 208 volt rating�

Single
phase

three

phase

Hp

AMpS

230v

208/230v

460/575v

SPL

UP TO 22�0 10 AWG

5�0

8 AWG

12 AWG

14 AWG

7�5

8 AWG

10 AWG

12 AWG

10�0

N/A

8 AWG

12 AWG

15�0

N/A

6 AWG

10 AWG

25�0

N/A

3 AWG

8 AWG

Recommended wire sizes may be larger than the minimum set up by
local ordinances. If so, the larger size wire should be used to prevent
excessive line voltage drop. The additional wire cost is very small
compared with the cost of repairing or replacing a motor electrically
“starved” by the use of supply wires which are too small.

figure 5

- Shut-off valve

www.CH-Commercial.com

7

Advertising
This manual is related to the following products: