LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 12

Advertising
background image

Rheos+ Boiler and Water Heater

Page 11

1. The figure in this addendum shows the

requirements for mechanical vent terminal

clearances for the U.S. and Canada.

2. Vent terminals for condensing appliances or

appliances with condensing vents are not

permitted to terminate above a public walkway,

or over an area where condensate or vapor could

create a nuisance or hazard.

3. Locate the vent terminal so that vent gases cannot

be drawn into air conditioning system inlets.

4. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows,

gravity inlets or other openings. Whenever

possible, locations under windows or near doors

should be avoided.

5. Locate the vent terminal so that it cannot be

blocked by snow. The installer may determine

that a vent terminal must be higher than the

minimum shown in codes, depending upon local

conditions.

6. Locate the terminal so the vent exhaust does

not settle on building surfaces or other nearby

objects. Vent products may damage such

surfaces or objects.

7. If the boiler or water heater uses ducted

combustion air from an intake terminal located

on the same wall, locate the vent terminal at least

3 feet (0.9m) horizontally from the combustion

air terminal, and locate the vent terminal at least

1 foot (0.3m) above the combustion air terminal.

From Massachusetts Rules and Regulations

248 CMR 5.08:

(a) For all side wall horizontally vented gas

fueled equipment installed in every dwelling,

building or structure used in whole or in

part for residential purposes, including those

owned or operated by the Commonwealth and

where the side wall exhaust vent termination

is less than seven (7) feet above finished grade

in the area of the venting, including but not

limited to decks and porches, the following

requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE

DETECTORS

At the time of installation of the side wall

horizontal vented gas fueled equipment, the

installing plumber or gasfitter shall observe that

a hard-wired carbon monoxide detector with

an alarm and battery back-up is installed on

the floor level where the gas equipment is to be

installed. In addition, the installing plumber or

gasfitter shall observe that a battery operated or

hard-wired carbon monoxide detector with an

alarm is installed on each additional level of the

dwelling, building or structure served by the side

wall horizontal vented gas fueled equipment.

It shall be the responsibility of the property

owner to secure the services of qualified licensed

professionals for the installation of hard-wired

carbon monoxide detectors.

a. In the event that the side wall horizontally

vented gas fueled equipment is installed in a

crawl space or an attic, the hard-wired carbon

monoxide detector with alarm and battery

back-up may be installed on the next adjacent

floor level.

b. In the event that the requirements of this

subdivision cannot be met at the time of

completion of installation, the owner shall

have a period of thirty (30) days to comply

with the above requirements; provided,

however, that during said thirty (30) day

period, a battery operated carbon monoxide

detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE

DETECTORS

Each carbon monoxide detector as required

in accordance with the above provisions shall

comply with NFPA 720 and be ANSI/UL 2034

listed and IAS certified.

3. SIGNAGE

A metal or plastic identification plate shall be

permanently mounted to the exterior of the

building at a minimum height of eight (8) feet

above grade directly in line with the exhaust vent

terminal for the horizontally vented gas fueled

heating appliance or equipment. The sign shall

read, in print size no less than one-half (½) inch

in size, “GAS VENT DIRECTLY BELOW.

KEEP CLEAR OF ALL OBSTRUCTIONS."

4. INSPECTION.

The state or local gas inspector of the side

wall horizontally vented gas fueled equipment

shall not approve the installation unless, upon

inspection, the inspector observes carbon

monoxide detectors and signage installed in

accordance with the provisions of 248 CMR

5.08(2)(a) 1 through 4.

(b) EXEMPTIONS: The following equipment is

exempt from 248 CMR 5.08(2)(a) 1 through 4:

1. The equipment listed in Chapter 10 entitled

“Equipment Not Required To Be Vented” in the

most current edition of NFPA 54 as adopted by

the Board; and

2. Product Approved side wall horizontal vented

gas fueled equipment installed in a room or

structure separate from the dwelling, building or

structure used in whole or in part for residential

purposes.

Advertising
This manual is related to the following products: