Page 43

8. Clean the heat exchanger: A light accumulation

of soot or corrosion on the outside of the heat

exchanger can be easily removed. Use a wire

brush to remove loose soot and scale from the

heat exchanger. Do not use water or compressed

air for cleaning.

9. NOTE: While the heat exchanger is out of the

unit, inspect the firewall refractory insulation

blocks for cracks, wear and breakage. Replace if

necessary.

10. Inspect the inside of the copper tubes for scale

buildup. Scale can build up on the inner surface

of the heat exchanger tubes, which can restrict

water flow. If the tubes show signs of scaling,

clean the internal surface. LAARS offers a tube

cleaning kit part number R2000700.

11. Reassemble in the reverse order.

If heat exchanger removal is necessary, consult

the factory for instructions.

NOTE: The Warranty does not cover damage
caused by lack of required maintenance, lack of
water flow, or improper operating practices.

The condensing (stainless steel) heat exchanger

is not in the firing chamber, so it will not experience

sooting. If there is fouling on the stainless steel heat

exchanger, or if it needs to be changed, contact the

factory.

7.2.17 Normally Open Vent Valve

Some Rheos+ models provide a normally open

vent valve for installations with IRI code requirements.

The valve opens when power is removed from the

safety valves. And the valve closes when the safety

valves are powered. See Section 3.1 item #4 for

installation instructions.

7.2.18 Motorized Safety Valve

Control packs B and E have an additional

motorized safety valve. This valve is powered open

at the same time as the safety valve. To remove the

valve actuator, shut off the 120V power and the gas

shutoff valve. Remove the right side, or front panel.

Disconnect the 120V wires from the actuator. Remove

the valve actuator by taking out the four screws, and

pulling the actuator out. Re-install in reverse order.

Turn on gas shutoff valve and 120V power and

check appliance operation and tightness of gas valve

connections.

The gas valve body will rarely have to be

removed. If there is a valve problem, and it has been

determined the actuator is working properly, the gas

valve body may need to be replaced. To remove the

gas valve body, shut off 120V power and the gas

shutoff valve. Remove the right side and front panels.

Remove the valve actuator. Unscrew the valve body

from the gas train. After the valve has been removed,

replace with a new valve in reverse order. Turn on gas

shutoff valve and 120V power and check appliance

operation and tightness of gas valve connections.

7.2.19 Gas Pressure Switches

The high and low gas pressure switches are 24V

manual reset switches that act to cut power to the gas

valves if the gas pressure is too low or too high for

proper operation. The gas pressure switches used are

integrally vent limited, and do not require venting to

atmosphere. To remove a switch, remove the screw

on the plastic housing and pull the clear cover off.

Disconnect the two wires from the screw terminals.

Twist the switch off the pipe nipple. Reassemble in

reverse order. For natural gas, set the low gas pressure

switch to 3" w.c. For propane, set the low gas pressure

switch to 5" w.c. For natural and propane, set the high

gas pressure switch to 14".

Section 8

TROuBLESHOOTING

8.1 Sequence of Operation

The Rheos+ appliance is a cold start appliance

that should start only on a call for heat from a tank

aquastat, room thermostat, zone valve end switch or

other space temperature control device.

1. Upon a call for heat,

(a) The internal pump will start.

(b) The blower will begin a 15 second pre-

purge.

2. Following the prepurge cycle the hot surface

ignitor will heat and will begin a 7 second trial

for ignition. The unit is allowed three attempts

for ignition.

3. The gas valve will then be energized and low-

fire (50% of full fire) ignition will occur. The

unit will remain in a low-fire start-up period for 15

seconds.

4. After the low-fire start time is over, the unit

will be in normal operation firing rate and will

modulate based on the heating load via the

temperature controller settings and readings.

5. The mixing system control will sense the water

temperature entering the copper heat exchanger,

and will change the positions of the mixing

valves to divert enough hot water from the

copper heat exchanger outlet back to its inlet

to keep the inlet at a minimum 140°F (60°C).

Therefore, when the return water temperature is

140°F (60°C) or lower, the outlet temperature

will be 160-165°F (71-74°C). With return

temperatures greater than 140°F (60°C), the

temperature rise across the Rheos+ is 20-25°F

(11-14°C), when the Rheos+ is at high firing rate.