LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 9

Advertising
background image

LAARS Heating Systems

Page 8

2.1.2 Intake Combustion Air

The combustion air can be taken through the

wall, or through the roof. When taken from the wall,

it must be taken from out-of-doors by means of the

LAARS horizontal wall terminal, shown in Table 3.

See Table 2 to select the appropriate diameter air pipe.

When taken from the roof, a field-supplied rain cap or

an elbow arrangement must be used to prevent entry of

rain water (see Figure 2).

Section 2

VENTING AND COMBuSTION AIR

2.1 Combustion Air

Rheos+ boilers and water heaters must have

provisions for combustion and ventilation air in

accordance with the applicable requirements for

Combustion Air Supply and Ventilation in the National

Fuel Gas Code, ANSI Z223 1; or in Canada, the

Natural Gas and Propane Installation Code, CSA

B149.1. All applicable provisions of local building

codes must also be adhered to.

A Rheos+ unit can take combustion air from the

space in which it is installed, or the combustion air can

be ducted directly to the unit. Ventilation air must be

provided in either case.

2.1.1 Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate

with the outdoors in accordance with method 1 or 2,

which follow. Where ducts are used, they shall be of

the same cross-sectional area as the free area of the

openings to which they connect.

Method 1: Two permanent openings, one

commencing within 12" (300mm) of the top and one

commencing within 12" (300mm) of the bottom, of

the enclosure shall be provided. The openings shall

communicate directly, or by ducts, with the outdoors

or spaces that freely communicate with the outdoors.

When directly communicating with the outdoors, or

when communicating to the outdoors through vertical

ducts, each opening shall have a minimum free area of

1 square inch per 4000 Btu/hr (550 square mm/kW) of

total input rating of all equipment in the enclosure. When

communicating to the outdoors through horizontal ducts,

each opening shall have a minimum free area of not less

than 1 square inch per 2000 Btu/hr (1100 square mm/kW)

of total input rating of all equipment in the enclosure.

Method 2: One permanent opening, commencing

within 12" (300mm) of the top of the enclosure, shall

be permitted. The opening shall directly communicate

with the outdoors or shall communicate through a

vertical or horizontal duct to the outdoors or spaces

that directly communicate with the outdoors and shall

have a minimum free area of 1 square inch per 3000

Btu/hr (734 square mm/kW) of the total input rating of

all equipment located in the enclosure. This opening

must not be less than the sum of the areas of all vent

connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform

to the requirements in the applicable codes listed

above.

In Canada, consult local building and safety

codes or, in absence of such requirements, follow

CAN/CGA B149.

Figure 2 - Combustion Air and Vent Through Roof

Use single-wall galvanized pipe for the

combustion air intake (see Table 4), sized per Section

1.8. Route the intake to the heater as directly as

possible. Seal all joints with tape. Provide adequate

hangers. The unit must not support the weight of the

combustion air intake pipe. Maximum linear pipe

length allowed is 50 feet (15.2m). Up to five elbows

can be used with the 50 feet of pipe. Subtract 10

allowable linear feet for every additional elbow used.

Model

Horizontal Combustion

Horizontal Vent

Air Terminal

Terminal

1200

20260701

D2004500

1600

20260703

D2004500

2000

20260703

D2004600

2400

20260703

D2006200

Table 3 - Horizontal Vent and Air Terminals

for Indoor Installations

Wall or

parapet

Advertising
This manual is related to the following products: