LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 13

Advertising
background image

LAARS Heating Systems

Page 12

(c) MANUFACTURER REQUIREMENTS

– GAS EQUIPMENT VENTING SYSTEM

PROVIDED. When the manufacturer of

Product Approved side wall horizontally

vented gas equipment provides a venting

system design or venting system components

with the equipment, the instructions provided

by the manufacturer for installation of the

equipment and the venting system shall

include:

1. Detailed instructions for the installation of the

venting system design or the venting system

components; and

2. A complete parts list for the venting system

design or venting system.

(d) MANUFACTURER REQUIREMENTS

– GAS EQUIPMENT VENTING SYSTEM

NOT PROVIDED. When the manufacturer

of a Product Approved side wall horizontally

vented gas fueled equipment does not

provide the parts for venting the fuel gases,

but identifies “special venting systems”, the

following requirements shall be satisfied by

the manufacturer:

1. The identification of each “special venting

system” shall include either the listing of the

website, phone number or manufacturer’s address

where the venting system installation instructions

can be obtained; and

2. The “special venting systems” shall be Product

Approved by the Board, and the instructions

provided with that system shall include a parts

list and detailed installation instructions.

(e) A copy of all installation instructions for the

Product Approved side wall horizontally

vented gas fueled equipment, and all the

venting instructions, parts lists, and/or design

instructions for the venting system shall

remain with the appliance or equipment at the

completion of the installation.

Manufacturers' websites where venting system

installation instructions may be obtained is

located on the Laars website at: http://www.

laars.com.

2.3.2 Side Wall Combustion Air Terminal

The Laars side wall combustion air terminal (see

Table 4) must be used when the heater takes air from a

side wall. Consider the following when installing the

terminal:

1. Do not locate the air inlet terminal near a source

of corrosive chemical fumes (e.g., cleaning fluid,

chlorine compounds, etc.)

2. Locate the terminal so that it will not be subject

to damage by accident or vandalism. It must be at

least 7 feet (2.1m) above a public walkway.

3. Locate the combustion air terminal so that it

cannot be blocked by snow. The National Fuel

Gas Code requires that it be at least 12 inches

(30cm) above grade, but the installer may

determine it should be higher, depending upon

local conditions.

4. If the Rheos is side-wall vented to the same wall,

locate the vent terminal at least 3 feet (0.9m)

horizontally from the combustion air terminal,

and locate the vent terminal at least 1 foot (0.3m)

above the combustion air terminal (see Figure 3).

2.3.3 Vertical Vent Terminal

When the unit is vented through the roof, the

vent must extend at least 3 feet (0.9m) above the point

at which it penetrates the roof. It must extend at least

2 feet (0.6m) higher than any portion of a building

within a horizontal distance of 10 feet (3.0m), and high

enough above the roof line to prevent blockage from

snow. When the combustion air is taken from the roof,

the combustion air must terminate at least 12" (30cm)

below the vent terminal (see Figure 2).

2.3.4 Vertical Combustion Air Terminal

When combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must

be used to prevent entry of rain water (see Figure 2).

The opening on the end of the terminal must be at least

12" (30cm) above the point at which it penetrates the

roof, and high enough above the roof line to prevent

blockage from snow. When the vent terminates on the

roof, the combustion air must terminate at least 12"

(30cm) below the vent terminal.

2.4 Common Vent Test — Boilers

NOTE: This section does not describe a method for

common venting Rheos+ units. It describes what must
be done when a unit is removed from a common vent

system. Rheos+ units require special vent systems

and fan for common vent. Contact the factory if you

have questions about common venting Rheos+ units.

When an existing boiler is removed from a

common venting system, the common venting system

is likely to be too large for proper venting of the

appliances remaining connected to it.

Advertising
This manual is related to the following products: