LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 16

Advertising
background image

Rheos+ Boiler and Water Heater

Page 15

medium is piped in parallel with the boiler with

appropriate valves to prevent the chilled medium from

entering the boiler.

The boiler piping system of a hot water heating

boiler connected to heating coils located in air

handling appliances where they may be exposed to

refrigerated air circulation must be equipped with flow

control valves or other automatic means to prevent

gravity circulation of the boiler water during the

cooling cycle.

A boiler installed above radiation level, or as

required by the authority having jurisdiction, must be

provided with a low water cutoff device either as a part

of the boiler or at the time of boiler installation.

4A.3 Freeze Protection – Boiler

Rheos+ units are not designed to be placed

outdoors, due to the potential for condensate to freeze

in the unit.

Proper precautions for freeze protection are

recommended for boiler installations in areas where

the danger of freezing exists.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices,

etc., may prevent a boiler from firing. Any time a

boiler is subjected to freezing conditions, and the

boiler is not able to fire, and/or the water is not able

to circulate, there is a risk of freezing in the boiler

or in the pipes in the system. When water freezes,

it expands. This can result in bursting of pipes in the

system, or damage to the boiler, which could result in

leaking or flooding conditions.

Do not use automotive anti-freeze. Maintaining

a mixture of minimum 50% water and maximum

50% properly inhibited HVAC glycol, which contains

an antifoamant, is the preferred method of freeze

protection for Rheos+ boilers. The percentage of

glycol used in the Rheos+ boiler must not exceed

50%. Typically, this mixture will serve as burst

protection for temperatures down to approximately

–35°F (-30°C).

IMPORTANT NOTES

: Different glycol products

may provide varying degrees of protection. Glycol

products must be maintained properly in a heating

system, or they may become ineffective. Consult

the glycol specifications, or the glycol manufacturer,
for information about specific products, maintenance

of solutions, and set up according to your particular

conditions.

For installations where temperatures are

expected to fall below 15°F inside the boiler cabinet,

the actuating gas valve must be equipped with a gas

valve heater, LAARS part number R2010100. Note

that some gas trains such as the IRI option may have

double actuators, and may require 2 gas valve heaters.

Section 4B
WATER CONNECTIONS —

RHEOS+ WATER HEATER

4B.1 Water System Piping —

Water Heater

Hot water piping should be supported by

suitable hangers or floor stands. Do not support piping

with this appliance. Due to expansion and contraction

of copper pipe, consideration should be given to the

type of hangers used. Rigid hangers may transmit

noise through the system resulting from the piping

sliding in the hangers. It is recommended that padding

be used when rigid hangers are installed.

The Rheos+ can be used with several different

types of readily available storage tanks. A pump

draws water from the storage tank and pumps the

water through the heater and back into the tank.

Pump-mounted units have a circulating pump built

into the water heater.

Pipe the outlet from the heater’s relief valve

such that any discharge from the relief valve will be

conducted to a suitable place for disposal when relief

occurs. Do not reduce line size or install any valves in

this line. The line must be installed to allow complete

drainage of both the valve and the line.

Suggested piping diagrams are shown in Figures

8, 9, 10, and 11. These diagrams are meant only as a

guide. Components required by local codes must be

properly installed.

The minimum inlet water temperature for the

Rheos+ is 50°F (10°C) to avoid condensing on the

copper coils.

4B.2 Hot Water Supply Piping —

Water Heater

Follow the tank manufacturer’s guidelines for

completion of the hot water system connections.

NOTE: A listed temperature and pressure relief
valve listed as complying with the Standard for
Relief Valves and Automatic Gas Shutoff Devices
for Hot Water Supply Systems, 1). ANSI Z21.22
latest edition, or 2). CSA 4.4, of suitable discharge
capacity must be installed in the separate storage
tank system.

If the Rheos+ water heater is installed in a

closed water supply system, such as one having a

backflow preventer in the cold water supply line, the

relief valve may discharge periodically, due to thermal

expansion. Means (such as a properly-sized expansion

tank) shall be provided to control thermal expansion.

Contact the water supplier or local plumbing inspector

on how to control this situation.

Advertising
This manual is related to the following products: