LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 15

Advertising
background image

LAARS Heating Systems

Page 14

7. All threaded joints should be coated with

piping compound resistant to action of liquefied

petroleum gas.

8. The appliance and its individual shutoff valve

must be disconnected from the gas supply piping

during any pressure testing of that system at test

pressures in excess of 1/2 PSIG (3.45kpa).

9. The unit must be isolated from the gas supply

system by closing its individual manual shutoff

valve during any pressure testing of the gas

supply piping system at test pressures equal to or

less than 1/2 PSIG (3.45kpa).

10. The appliance and its gas connection must be

leak tested before placing it in operation.

11. Purge all air from gas lines.

WARNING

Open flame can cause gas to ignite and result in
property damage, severe injury, or loss of life.

NOTE: The Rheos+ appliance and all other gas

appliances sharing the gas supply line must be firing

at maximum capacity to properly measure the inlet

supply pressure. The pressure can be measured at

the supply pressure port on the gas valve. Low gas

pressure could be an indication of an undersized

gas meter, undersized gas supply lines and/or an

obstructed gas supply line. A bleed line from the

diaphragm-type automatic valve shall be vented per

local code requirements. Rheos+ units are equipped

with low and high gas pressure switches that are

integrally vent limited. These types of devices do not

require venting to atmosphere.

Section 4A

WATER CONNECTIONS —
RHEOS+ BOILER

4A.1 Heating System Piping:

Hot Supply Connections — Boiler

NOTE: This appliance must be installed in a closed

pressure system with a minimum of 12 psi (82.7kPa)

static pressure at the boiler.

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with

this appliance. Due to expansion and contraction of

copper pipe, consideration should be given to the type

of hangers used. Rigid hangers may transmit noise

through the system resulting from the piping sliding in

the hangers. It is recommended that padding be used

when rigid hangers are installed. Maintain 1" (2.5cm)

clearance to combustibles for hot water pipes.

Pipe the discharge of the relief valve (full size)

to a drain or in a manner to prevent injury in the event

of pressure relief. Install an air purger, an air vent,

a diaphragm-type expansion tank, and a hydronic

flow check in the system supply loop. Minimum fill

pressure must be 12psig (82.7kPa). Install shutoff

valves where required by code.

Suggested piping diagrams are shown in Figures

4, 5, and 6. These diagrams are meant only as a guide.

Components required by local codes must be properly

installed. The Rheos+ boiler’s efficiency is higher with

lower return water temperatures. Therefore, to get the

most of low return temperature with multiple boilers,

pipe as shown in Figure 4.

The Rheos+ boiler has an internal mixing

system that ensures that the condensation does not

occur on the finned copper heat exchanger, with

boiler return temperature down to 50°F (10°C). This

system, that consists of automatically actuated

and linked valves, is set up at the factory, and is

non-adjustable. The return water goes through the

stainless steel heat exchanger, then to the mixing

system (see Figure 7).

If the water at the inlet of the copper heat

exchanger is less than 140°F (60°C), water from the

outlet of the copper heat exchanger will be directed

back to the inlet of the copper heat exchanger, and will

mix to bring the inlet water up to 140°F (60°C). Once

through the copper heat exchanger, the water picks up

another 20-25°F (11-14°C) (when at high fire), and

it leaves the boiler at 160-165°F (71-74°C). This hot

water is then sent to the system.

If the water at the inlet of the copper heat

exchanger is 140°F (60°C), or higher, the water will be

allowed to flow through the copper heat exchanger and

directly to the outlet of the Rheos+, and there will be a

20-25°F (11-14°C) temperature rise between the inlet

and outlet of the unit, when the unit is at high fire.

The pump in the boiler is sized for the boiler’s

heat exchangers, the internal mixing system, and 30

feet of full-sized piping, with a normal number of

fittings taken into consideration. The piping must be

primary/secondary, ensuring that the boiler’s pump is

only used for the boiler, and that the system pump(s)

do not interfere with the Rheos+ pump or mixing

system.

The minimum inlet water temperature for the

Rheos+ is 50°F (10°C) to avoid condensing on the

copper coils.

4A.2 Cold Water Make-up — Boiler

1. Connect the cold water supply to the inlet

connection of an automatic fill valve.

2. Install a suitable back flow preventer between the

automatic fill valve and the cold water supply.

3. Install shut off valves where required.

NOTE: The boiler, when used in connection with a

refrigeration system, must be installed so the chilled

Advertising