1 introduction, 2 model identification, Model designation – LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 6

Advertising
background image

Rheos+ Boiler and Water Heater

Page 5

Section 1

GENERAL INFORMATION

USING THIS MANUAL – Because the

Rheos+ Boilers and Rheos+ Water Heaters are

identical appliances, with the exception of materials

of manufacture, labels and ultimate use application,

this manual provides information for the proper

installation, operation and maintenance of both

products. Where differences exist between the

application of the appliances and their operation,

the sections pertinent to only one appliance or the

other will be so identified.

WARNING

The Rheos+ hydronic, boiler or water heater

must

be installed in accordance with the procedures

detailed in this manual, or the LAARS Heating

Systems warranty will be voided. The installation

must conform to the requirements of the local

jurisdiction having authority, and, in the United

States, to the latest edition of the National Fuel

Gas Code, ANSI Z223.1/NFPA54. In Canada,

the installation must conform to the latest edition

of CSA B149.1 Natural Gas and Propane Gas

Installation Code, and/or local codes. Where
required by the authority having jurisdiction, the

installation of Rheos+ boilers must conform to

the Standard for Controls and Safety Devices

for Automatically Fired Boilers, ANSI/ASME
CSD-1. Any modifications to the boiler, its gas
controls, or wiring may void the warranty. If field
conditions require modifications, consult the factory
representative before initiating such modifications.

1.1 Introduction

This manual provides information necessary for

the installation, operation, and maintenance of LAARS

Heating Systems Rheos+ (copper tube or cupronickel

tubes) appliances. Read it carefully before installation.

All application and installation procedures

should be reviewed completely before proceeding

with the installation. Consult the LAARS Heating

Systems factory, or local factory representative, with

any problems or questions regarding this equipment.

Experience has shown that most operating problems

are caused by improper installation.

The Rheos+ appliance is protected against over

pressurization. A pressure relief valve is fitted to

all appliances. It is installed inside the jacket, at the

water outlet of the unit. (See Sections 4A and 4B for

instructions on how to install a relief valve outlet.)

IMPORTANT:

The inlet gas pressure to the appliance

must not exceed 13" W.C. (3.2kPa).

All installations must be made in accordance

with 1) American National Standard Z223.1/NFPA54-

Latest Edition “National Fuel Gas Code” or 2) CSA

B149.1 “Natural Gas and Propane Installation Code”

and with the requirement of the local utility or other

authorities having jurisdiction. Such applicable

requirements take precedence over the general

instructions contained herein.

All electrical wiring is to be done in accordance

with the local codes, or in the absence of local codes,

with: 1) The National Electrical Code ANSI/NFPA No.

70-latest Edition, or 2) CSA STD. C22.1 “Canadian

Electrical Code - Part 1”. This appliance must be

electrically grounded in accordance with these codes.

1.2 Model Identification

Consult the rating plate on the unit. The

following information describes the model number

structure.

(1-2) Model Series Designation

R H = Rheos+ mid-sized commercial

(3) Model Efficiency

H = High Efficiency (condensing)

(4) Usage

H = Hydronic

V = Volume Water

(5-8) Size

1 2 0 0 = 1,200,000 BTU/hr input

1 6 0 0 = 1,600,000 BTU/hr input

2 0 0 0 = 2,000,000 BTU/hr input

2 4 0 0 = 2,400,000 BTU/hr input

(9) Fuel

N = Natural Gas

P = Liquid Propane

(10) Altitude

A = Universal Altitude (0' to 10,000') (0m to 3050m)

(11) Location

I = Indoor

Model Designation

1

2

3

4

5

6 7 8

9

10

11

12

13

14

15 16

R H

H

0 0

A

I

F

SERIES

R

H

H

USAGE

H
V

SIZE

1

2

0

0

1

6

0

0

2

0

0

0

2

4

0

0

FUEL

N
P

ALTITUDE

A

FIRING

MODE

F

LOCATION

I

REVISION

1
2

HEAT

EXCHANGER

E
F

OPTION

CODES

X

A

H

B

N

F

S