Figure 7 - Internal Piping Schematic

4B.5 Freeze Protection – Water Heater

Rheos+ heaters are not designed to be placed

outdoors, due to the potential for condensate to freeze

in the unit.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices,

etc., may prevent a heater from firing. Any time a

heater is subjected to freezing conditions, and the

heater is not able to fire, and/or the water is not

able to circulate, there is a risk of freezing in the

heater or in the pipes in the system. When water

freezes, it expands. This can result in bursting of pipes

in the system, or damage to the heater, which could

result in leaking or flooding conditions.

For installations where temperatures are

expected to fall below 15°F inside the boiler cabinet,

the actuating gas valve must be equipped with a gas

valve heater, LAARS part number R2010100. Note

that some gas trains such as the IRI option may have

double actuators, and may require two gas valve

heaters.