SilentKnight SD500-AIM Addressable Input Module and SD500-MIM Addressable Mini-Input Module User Manual

Wiring the sd500-aim / mim, Specifications

Advertising
background image

P/N 151071

SD500-AIM Input Module and

SD500-MIM Mini Input Module

Installation Instructions

The following instructions are a quick reference
guide, refer to the control panel installation
manual P/N 151139, 151274, 151280, 151295,
151209, or 151302 for detailed system
information.

Wiring the SD500-AIM / MIM

Note: Installation and wiring of these devices must be done in

accordance with NFPA 72 and local ordinances.

Terminate the wiring as shown in Table 1. See
also Figure 1 or Figure 2

Specifications

Table 2 lists the operating specifications for the
SD500-AIM and the SD500-MIM.

Impedance for Earth Ground Fault is 0

Ω for all

terminals.

Figure 1: Class B Wiring the SD500-AIM & SD500-MIM

Table 1: Wire Connections

SD500-AIM

SD500-MIM

Terminals

To:

FACP or SLC

Loop Terminals

Contact

SLC

SLC

OUT

SC–

+

S+

Contact

A out

CLASS A

OR B

To N.O. Contact

B out

To N.O. Contact

A IN

CLASS A ONLY

(SD500-AIM Only)

End of Loop A

End of Loop B

B IN

Table 2: SD500-AIM and SD500-MIM Specifications

Specifications

Max. Line resistance

50

Ω

Max. Alarm
Current

One device in alarm
23mA. 46 mA for two
devices in alarm.

.5 mA for each addi-
tional device in
alarm.

Max. Voltage

33 V

Operating Temperature

0° to 49° C
(32° to 120° F)

Indoor use only

Table 2: SD500-AIM and SD500-MIM Specifications

Specifications