10
Step 1. Allow more than 10 seconds to elapse after removing the power cords from the VX-3000DS' rear-
mounted AC inlets (IN1 and IN2).
Step 2. Insert the positive battery cable into the VX-3000DS' rear-mounted BATTERY POWER IN positive
terminal from the bottom side of the connector, then tighten the terminal screw with a flat screwdriver.
Note
Never connect the negative cable first to avoid battery short-circuit that occurs if the positive cable
should contact the unit chassis or equipment rack.
Step 3. Connect the negative battery cable to the negative terminal in the same manner as Step 2.
VX-3000DS
Tightening torque: 6 – 8 Nm
3
2
Cable cross
sectional area
16 mm
2
25 mm
2
35 mm
2
50 mm
2
180 cm
280 cm
400 cm
570 cm
AWG 6
AWG 4
AWG 2
AWG 0 (AWG 1/0)
80 cm each
130 cm each
190 cm each
275 cm each
20 cm
20 cm
20 cm
20 cm
Length (2 mΩ)
AWG
Example of wire length
Cable A, Cable C Cable B
VX-3000DS’ Battery connection terminals
Battery terminals
6 – 8 Nm
4.1 – 5.6 Nm (M6)
8.2 – 5.6 Nm (M8)
• Use the battery connection cables as short in length and as large in diameter as possible.
Battery connnection terminals
Battery
Cable A
Cable C
Cable B
Battery
VX-3000DS
TEMPER
ATURE
SENSOR
24V(16-25V)
POWER OUT
MAX 0.3A
IN
OUT
DS LINK
• Total resistance of the battery connection path should be less than 4 mΩ, which includes resistance of all of
wire, terminal, fuse, and terminal points.
For reference, refer to each resistance as follows.
Resistance of terminal, fuse (if provided): 1 – 2 mΩ
Resistance of terminal point:
0.1 – 0.5 mΩ
• Tighten the bolts, nuts, and screws of the unit's battery connection terminals and battery terminals with the
torque as shown below.