Vx-3000ds, Temperature sensor – Toa VX-3000DS CE-GB User Manual

Page 26

Advertising
background image

26

VX-3000DS

The power manager VX-3000DS monitors the availability of the AC power and switches on the battery in case

of a total loss of that power.

When the AC power is available, then the batteries will be charged. The charge current is monitored, and when

it is below 2 mA, then a charger fault will be entered into the log file of the system. The indications “BATTERY

CONNECT“ and “CHARGING“ do not light.
The battery surveillance of the VX-3000DS measures the resistance of the battery circuit at the set intervals. A

battery fault will be logged when this resistance is higher than the initial value set by the DIP switch (p. 6).

The indication “BATTERY CONDITION“ extinguishes. The battery test can be proceeded by pushing the button

“BATTERY CHECK“.

The VX-3000DS should be installed at a low position in the cabinet rack.

Temperature Sensor

Purpose and Characteristics
The temperature sensor measures the ambient temperature of the battery to control the charging voltage.

When the voltage is too high, then the battery can produce gas that can cause the battery to break. The gas can

leak through the pressure control valve and develop an explosive gas, therefore the cabinet rack and the room

must be vented. The battery cannot be charged fully when the charging voltage is too low. When the current into

the battery is less than 2 mA, then a charger error will be logged and the “Charge” LED extinguishes.

The temperature sensor must not be disconnected during charging of the battery because then the charging

voltage becomes high causing the dangerous situations explained above. When exchanging the temperature

sensor, the charging voltage of the VX-3000DS must be re-adjusted by TOA dealer.

Installation

In opposition to the battery, the temperature sensor reacts on ambient temperature changes, therefore it must

not be exceeded to such changes. Such can occur near temperature-controlled fans as in the VX-3000DS.

We recommend to provide vents at the cabinet rack’s bottom and top to allow the development of a constant

airstream from bottom to top (chimney effect). This reduces warm air from the devices swapping randomly

inside the cabinet that can cause a randomly occurring charger fault.

device

device

device

Temperature sensor

too high

device

Battery

VX-3000DS

No bottom vent

irregular air flow

Temperature sensor fixed

by thermal insulating sheet

at side of the battery

Temperature sensor

too close to fan

device

device

device

Battery

VX-3000DS

Vent near

bottom

device

device

device

Battery

VX-3000DS

Figure 3: Incorrect and correct positioning of the temperature sensor in the cabinet rack

The temperature sensor can be placed between 2 batteries by fixing it on one of them using the supplied

thermal insulating sheet. Do not damage the temperature sensor when pushing the batteries together.

The temperature sensor cable can be expanded by some metres causing no problems.