Check procedure 2:

This measurement can be done with a slow voltmeter.

Disconnect the VA unit’s power supply from the DC output from the VX-3000DS and connect a load of 5 - 6 Ω /

600 W to the DC output (when the current of the connected system components is known), then take care that

the total current is approximately 5 A. Do not measure a too long time to avoid reducing the battery’s capacity

too much.

Measure the voltage of each cable path while the load is connected.

measuring Points

Touch the battery contacts and the screw tops of the battery connector of the VX-3000DS with the measuring

tips as shown above.

Do not measure the voltage at the cable clamps, because in this case the contact resistance is excluded from

the measurement.

Measure the voltage on each path (it may contain a fuse).

Add these voltages and divide by 5 (5 A current).

The result is the resistance. When it exceeds 0.004 Ω, then check the contacts, clean them if necessary and

tighten it. Alternative: max. voltage = 20 mV.

Example:

Current I = 5 A, measured voltages: 1 : 120 mV, 2 : 10 mV, 3 : 50 mV

Total voltage: 180 mV = 0.18 V. R = 0.18 V/ 5 A = 0.036 Ω > 0.004 Ω

The total resistance is too high. Since path 1-1 has a much higher resistance than path 3-3, its connection

should be checked.

When the resistance is below 0.004 Ω, then the battery can be defective (too old).

measuring the battery’s internal resistance

There are special but expensive measuring tools for battery impedances. Usually when the battery’s internal

impedance is double than typical, then the battery should be exchanged.