[Fault indication]

If any of the following indicators on the front panel remains unlit, the unit is judged failed. In such cases, remove

the cause of the failure, and restore the unit to normal operation.

• Power indicators [AC POWER IN1, IN2]

• Battery connection indicator [BATTERY CONNECT]

• Charging indicator [CHARGING]

• Battery check indicator [BATTERY CONDITION]

Note

Even if any of these indicators flashes, this does not indicate malfunction.

[Front (with the front panel removed)]

9

7 8

7. DIP switch

8

1

ON
OFF

• Switches 1 and 2 are not used.

Be sure to leave both switches OFF.
• Switches 3 – 8 are factory-preset as shown below.

Switches 3 and 5:

ON

Switches 4 and 6 – 8: OFF
Each switch function is described as follows.

Switch 3

Used for terminating the connection.

Set to ON when no other VX-3000DS unit is

connected or when this unit is the last one of

connected units.

Switches 4 and 5

Set the upper limit value of the internal battery

resistance and battery connection cable resistance

to be monitored for fault detection.

Setting switch combination of 4 and 5 is as follows.

5

ON

OFF

4

ON

25 mΩ*

1

100 mΩ

OFF

50 mΩ

DISABLE

*

1

Settings compliant with EN 54-4.

Switch 6

Sets the battery charging current.

ON: 11 A (100 to 200 Ah)

OFF*

2

: 5.5 A (under 100 Ah)

*

2

Settings compliant with EN 54-4.

Switch 7

Sets whether the failure detection function is used

for the AC Power IN2.

ON: Failure detection function disabled.

OFF*

3

: Failure detection function enabled.

*

3

Settings compliant with EN 54-4.

Set to ON when using the AC Power IN1 only, and

set to OFF when using both AC Power IN1 and IN2.

Note

The AC inlet IN2 works irrespective of Switch 7

setting as long as power is applied to it. Therefore,

be sure to set Switch 7 to OFF (enabling the failure

detection function) whenever IN2 is used.

Switch 8

Places the unit in AC operation mode or battery

mode.

ON: All power outputs are shut down when AC

power fails even if backup batteries are

connected. (AC operation mode).

OFF: Battery is used as backup power supply

when AC power fails. (Battery mode)

Be sure to set to OFF in normal operation.

8. Shutdown button

Pressing this button forcibly shuts down this unit

irrespective of Switch 8 ON/OFF setting of the DIP

switch (7).

9. Reset button

Pressing this button resets this unit.