Installating Vent/Combustion Air & Condensate Drain

When selecting and installing a conden-
sate pump, ensure the pump is approved
for use with condensing boilers and fur-
naces. The pump should be equipped
with an overflow switch to prevent prop-
erty damage from potential condensate
spillage.

8. The PRESTIGE Solo will typically produce

a condensate that is considered slightly
acidic with a pH content below 3.0. Install
a neutralizing filter if required by authority
having jurisdiction.

The condensate drain must remain filled
and unobstructed and allow unrestricted
flow of condensate. The condensate
should not be subject to conditions
where freezing could occur. If the con-
densate is subjected to freezing or
becomes obstructed , it can leak, result-
ing in potential water damage to the boil-
er and surrounding area.

NOTICE

CAUTION

Flexible Tubing

(or 3/4 PVC/

CPVC Piping

to Drain)

Compression

Nut with Rubber Seal

Fill Plug

with Vaccum

Break Port

Condensate

Drain Assembly

Plastic Ball

Retaining Nut

with Rubber Seal

(Hand Tight Only)

Heat Exchanger

Condensate

Drain Nipple

Fig. 15: Condensate Drain Assembly