Start-Up Procedures

STANDBY, no demand for heat

Fan prepurge or post purge cycle

Ignition sequence

Burner ON for space heating (CH)

Burner ON for domestic hot water (DHW)

Pre-check for air flow prior to prepurge cycle

Burner OFF due to reaching temperature setpoint

Domestic hot water (DHW) post pump cycle

Space Heating (CH) post pump cycle

Burner blocked:

Supply temperature too high (202 F) . Burner

will remain OFF until temperature drops

below 200 F

Return temperature too high (202 F). Burner

will remain OFF until temperature drops

below 200 F

Return temperature is higher than

supply temperature. Burner will remain OFF

until corrected.
Supply temperature increased too quickly.

Burner will remain OFF for a 10 minute period.

Burner will recycle, increasing waiting period 1

minute for a max. 15 minutes

Factory supplied LWCO device or

external limit (terminals 15 & 16) is OPEN.

Burner off for 150 seconds, auto reset.

0
1

180
180
180
180
180

180
180
180
180
180

2
3
4
5
6
7
8
9

18

b

19

b

24

b

25

b

26

b

2

Display

Boiler function

No blower signal
Blower signal present with no demand, Burner

will remain OFF until condition terminates

Temperature difference between the supply and

return is more than 72 F. Burner will remain OFF

for 150 seconds. Burner will recycle increasing

wating period 1 minute for a max. 20 cycle.

Flue temperature sensor is short-circuited.

Burner OFF until corrected

Flue temperature senor is “open” Burner OFF

until corrected.

Flue temperature greater than 240 F but less

than 250 F. Burner off for 150 seconds

Wait for the blower to start

8

b

2

2

9

b

30

b

35

b

40

b

Indirect water heater temperature sensor is

short-circuited. Burner OFF until corrected.
Indirect water heater temperature sensor is

“open” or disconnected. Burner OFF until

corrected.