Start-Up Procedures

Error (Hard Lockout) Mode

If a serious fault occurs, the system enters a
hard lockout condition which requires a manu-
al reset by pressing the RESET button. A hard
lock is indicated by displaying an E for the first
digit, followed by the error code.

For a detailed description of the error codes, ref-
erence the PRESTIGE Solo Troubleshooting
Guide.

The boiler freeze protection feature is
disabled during a Hard Lockout, howev-
er the CH circulator will operate.

During a hard lockout or low water con-
dition the boiler will not re-start without
service. If the heating system is left unat-
tended in cold weather appropriate safe-
guards or alarms should be installed to
prevent property damage.

CAUTION

CAUTION

Gas valve harness not properly connected

Failed ignition after 5 attempts

Power supply lost after lockout occured

Internal control failure

Internal control failure

E
E

02
03
04

08

09

E
E

E

Display

Hard Lockout

Internal control failure

05

E

Internal control failure

06

E

Internal control failure

07

E

Flame detected prior to burner startup

E 00

Internal control failure

External limit (terminals 13 & 14) is OPEN

Blower signal does not reset to zero

No blower signal present

Supply Temperature sensor is short circuited

11

12

15
16

29

28

E

E
E

E
E

E

Flue Temperature exceeds 250 F

52

E

Internal control error - failure to read parameters

61

E

Return Temperature sensor is short circuited

Supply Temperature sensor is OPEN

Return Temperature sensor is OPEN

Internal control failure

Internal control failure

Inadequate power supply to the fan

E
E

31
32

36
37

44

60

65

E
E

E

E
E

Flue Temperature sensor is short circuit

40

E

Return Temperature exceeds 212 F

Supply Temperature increased too rapidly

Internal control failure

Internal control failure

Internal control failure

Internal control failure

Internal control failure

17

19
25

13

E

E
E

E

Supply Temperature exceeds 212 F

18

E

E 14

Flue Temperature sensor is OPEN

35

E

E

Internal control failure

15

E

Supply or Return Temperature sensor drift

23

Invalid power frequency

Supply or Return Temperature failure

Supply or Return Temperature not changing

13

1

1

1
1
1

22

24

E

E
E