63

Maintenance Procedures

Check Flame Signal

The flame signal can be read from item E of the
information mode. It should be a min. 3μ Α −DC.

Check the ignitor for fouling or damaged
insulation if a low flame signal is read.

Check ground wiring and continuity as a cause
for low flame signal. Replace ignitor if condi-
tions are satisfactory.

Check Combustion Levels

Refer to page 41 of this manual for measuring
combustion levels and burner adjustments.

Check Flue Gas Temperature

1. Adjust the boiler to fire at HIGH fire, see

page 45. Place the control display to INFOR-
MATION mode, see page 47 for procedures.

2. The flue gas temperature is indicated on

the display when the first digit is 5. The
measured temperature (shown as the last 3
digits) should not be more than 54ºF high-
er than the measured supply water temper-
ature.

3. The measured supply water temperature is

indicated on the information display when
the first digit is 1 and the temperature
shown as the last 3 digits.

4. If the measured flue gas temperature is

higher than 54ºF over the supply water
temperature, shut the boiler down and fol-
low the procedures listed below to clean
the heat exchanger.

Clean Heat Exchanger

1. Shut down the boiler:

- Follow the instructions on Page 42 "To

Turn Off Gas to Appliance"

- Do not drain the boiler unless the boil-

er will be subject to freezing condi-
tions.

- Do not drain the boiler if freeze protec-

tion fluid is used in the system.

2. Allow the boiler to cool down to room tem-

perature before servicing.

3. Disconnect the gas piping and rectifier

plug to the gas valve.

4. Disconnect the wiring harness connectors

from the blower and remove the blower
retaining screws or nuts. Remove the blow-
er from the unit.

5. Remove the mounting nuts securing the

burner mounting plate to the heat exchang-
er and set aside.

6. Carefully remove the burner mounting

plate assembly from the heat exchanger.
Ensure combustion chamber insulation is
not damaged during removal of burner
mounting plate assembly. See WARNING
on page 64.

7. Carefully remove the combustion chamber

insulation from the heat exchanger and set
aside. See WARNING on page 64.

8. Use a vacuum cleaner, compressed air or

water to remove any accumulation from
the heat exchanger flue ways. Do not use
any solvent.

9. Re-install the combustion chamber insula-

tion onto the heat exchanger.

10. Re-assemble the burner mounting plate

assembly onto the heat exchanger. Ensure
the burner plate gasket and combustion
chamber insulation is in place and not dam-
aged, replace gasket and insulation if nec-
essary. See WARNING on page 64.

11. Re-assemble the blower onto the burner

mounting plate and reconnect the wiring
harness connectors.

12. Reconnect the gas piping and rectifier to

gas valve. Check for leaks, repair if neces-
sary.

13. Close isolation valves on the boiler water

piping to isolate the boiler from the heating
system.