External wiring – TriangleTube 399 Solo User Manual

Page 41

Advertising
background image

35

External Wiring

H

N

High Voltage

120

V.A.C.

24

V.A.C.

Room

Thermostat

Room

Thermostat

Zone 1

Zone 2

Additional zones

Additional zones may

be added as shown above

To Prestige

24V Terminal Strip

Transformer

(Power)

Zone

Valve

Zone Valve

7

8

To Prestige

24V Terminal Strip

H

N

High Voltage

120

V.A.C.

24

V.A.C.

Room

Thermostat

Room

Thermostat

Zone 1

Zone 2

Additional zones

Additional zones may

be added as shown above

Transformer

(Power)

Zone

Valve

Zone Valve

* Isolation relay

7

8

*Use isolation relay on

3-wire zone valve with

non-isolated end switch.

Transformer and the Prestige

MCBA control can burn out

if isolation relay is not used.

NOTICE:

4 Wire Zone Valve

3 Wire Zone Valve

Fig. 22: Multiple Zone Field Wiring Using Zone Valves