Stby, Coff, Doff – TriangleTube 399 Solo User Manual

Page 51

Advertising
background image

45

Start-Up Procedures

Boiler Control Display

Standby Mode

This is the standard mode for the PRESTIGE
Solo. The control automatically returns to this
mode after 20 minutes if no keys have been
pressed on the display. Any parameters that
were modified are then stored.

The first character shows (on left side of dis-
play) the current status of the boiler depending
on the condition of both the boiler and the
burner. The last 3 characters indicate the boiler
supply temperature.

If the burner is blocked due to a “soft” lockout,
the display alternates between a 9 followed by
the boiler supply temperature and a “b” with a
two digit error code.

TO TEMPORARILY PLACE THE BURN-
ER INTO HIGH FIRE TEST MODE:
press
the MODE button until “

StbY

” is displayed.

Then press and hold both the MODE and “+”
buttons simultaneously until the first digit
flashes “H”.

While in the test mode:

-

high limit will function

-

boiler CH circulator will function

-

domestic circulator will not function

-

the test mode will time out in approxi-
mately 10 minutes

TO TEMPORARILY PLACE THE BURN-
ER INTO LOW FIRE TEST MODE:
press
the MODE button until “

StbY

” is displayed.

Then press and hold both MODE and “-” but-
tons simultaneously until the first digit flashes
“L”.

TO DEACTIVATE THE HIGH OR LOW
FIRE TEST MODE:
press the MODE button
until “

StbY

” is displayed. Then press and

hold both the “+” and “-” buttons simultane-
ously to deactivate the high or low fire test
mode.

If the “+” button is held in, the CH system
(parameter 3) will be turned OFF and the
display will show

cOFF

. Press and

hold the “+” button to turn the CH sys-
tem back ON, the display will show “c”
followed by CH set point. If the “-” but-
ton is held in while in the

StbY

mode,

domestic system (parameter 2) will be
turned OFF and the display will show

dOFF

. Press and hold “-” button to

turn the domestic system back ON, the
display will show “d” followed by domes-
tic set point temperature.

StbY

NOTICE

Test function: Burner on, high fire mode

Test function: Burner on, low fire mode

180
180

H
L

Display

Boiler function