Pre-Installation Items

3

SECTION I - Pre-Installation Items

Code Compliance

This product must be installed in accordance to
the following:

-

All applicable local, state, national and
provincial codes, ordinances, regula-
tions and laws.

-

For installations in Massachusetts, code
requires the boiler to be installed by a
licensed plumber or gas fitter, and if
antifreeze is utilized, the installation of
a reduced pressure backflow preventer
device is required in the boiler’s cold
water fill or make up water supply line.

-

For installation in Massachusetts all direct
vented appliances must comply with the
guidelines as outlined on page 11.

- The National Fuel Gas Code NFPA54/

ANSI Z 223.1 - Latest edition.

-

National Electric Code ANSI/NFPA 70.

- For installations in Canada -“Installation

Code for Gas Burning Equipment”
CGA/B149.1 or B149.2 Canadian
Electrical Code Part 1 CSA C22.1.

-

Standards for Controls and Safety
Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1, when required.

The PRESTIGE Solo boiler gas manifold
and gas controls meet the safe lighting and
other performance requirements as speci-
fied in ANSI Z21.13 latest edition.

Determining Product Location

Before locating the PRESTIGE SOLO check
for convenient locations to:

-

Heating system piping

-

Venting

-

Gas supply piping

-

Electrical service

Ensure the boiler location allows the combus-
tion air/vent piping to be routed directly through
the building and terminate properly outside with
a minimum amount of length and bends.

Ensure the area chosen for the installation of the
PRESTIGE Solo is free of any combustible
materials, gasoline and other flammable liquids.

Failure to remove or maintain the area
free of combustible materials, gasoline
and other flammable liquids or vapors
can result in severe personal injury,
death or substantial property damage.

Ensure the PRESTIGE Solo and its controls
are protected from dripping or spraying water
during normal operation or service.

The PRESTIGE Solo should be installed in a
location so that any water leaking from the
boiler or piping connections or relief valve will
not cause damage to the area surrounding the
unit or any lower floors in the structure.

Boiler Replacement

If the PRESTIGE Solo is replacing an existing
boiler, the following items should be checked
and corrected prior to installation:

-

Boiler piping leaks and corrosion.

- Improper location and sizing of the

expansion tank on the boiler heating
loop.

-

If applicable, level and quality of freeze
protection within the boiler system.

Recommended Clearances

The PRESTIGE Solo is approved for zero
clearance to combustibles, excluding vent and
boiler piping.

-

Boiler Piping - 1/4 inch from com-
bustible materials.

NOTICE

WARNING