Riello manometers and vacuum gauges do

not require any adaptors, and can be safely

connected to the pump ports. An NPT (metric) adapter

must be used when connecting

other gauge models.

SINGLE LINE (GRAVITY FEED SYSTEM)

A)

The burner is shipped configured for use in single line applications. No changes to

the oil pump are required for use in single line applications.

NOTE; If the pump cover (1) is removed for any reason, be sure the 0-ring (2), is properly

seated in the pump cover (1) before re-attaching the pump cover to the pump housing.

SINGLE LINE SYSTEM - PIPE LENGTHS

H

3/8 ’ OD

1/2 ’ OD

FT

M

FT

M

FT

M

1.5

0.5

33

10

65

20

3.0

1.0

65

20

130

40

5.0

1.5

130

40

260

80

6.5

2.0

195

60

325

100

D6009

NOTE: Do not exceed pipe lengths

indicated in chart.

B)

Connect the pipe connector to the SUPPLY PORT (6) of the pump. Attach the required

piping to this pipe connector. Be sure that the plug in the RETURN PORT (9) is tightened

securely.