background image

SETTING THE AIR ADJUSTMENT PLATE

A)

Regulation of the combustion air flow is made by adjustment of the manual AIR

ADJUSTMENT PLATE (1) after loosening the FIXING SCREWS (2 & 3). The initial

setting of the air adjustment plate should be made according to Column 5 in the

Burner Set-up Chart.

B) The proper number on the manual AIR

ADJUSTMENT PLATE (1) should line up

with the SETTING INDICATOR (4) on the

fan housing cover. Once set, the air ad­

justment plate should be secured in place

by tightening SCREWS 2 and 3.

C)

The final position of the air adjustment

plate will vary on each installation. Use in­

struments to establish the proper settings

for maximum CO

2

and a smoke reading of

zero.

NOTE:

Variations in flue gas, smoke,

CO

2

and

temperature

readings

may

be

experienced when the burner cover is put

in

place.

Therefore,

the

burner

cover

must be in place when making the final

combustion

instrument

readings,

to

ensure proper test results.

BURNER SET-UP CHART

1

ACTUAL FIRING

RATE ± 5%

GPH

kg/h

NOZZLE

SIZE

PUMP

PRESSURE

GPH

PSI

BAR

TURBULATOR

SETTING

AIR DAMPER

SETTING

1.45

4.7

1.25x60°

145

10

1.5

2.7

1.80

5.8

1.50x60°

145

10

2.0

2.8

2.10

6.8

1.75x60°

145

10

2.5

3.1

2.40

7.8

2.00x60°

145

10

3.5

3.4

2.75

8.9

2.25x60°

150

10.4

4.0

4.2

2.95

9.5

2.50x60°

140

9.8

4.5

4.2

NOZZLES: Monarch R-PLP, Delavan W-B, Danfoss S-B, Steinen SS-S, Hago P.

NOTE: A 60° degree nozzle is suggested, however, a 80° degree nozzle may be
used in cases where the flame is unstable at light-off when operated at low ambient

temperatures.