ASSEMBLY OF AIR TUBE

TO BURNER CHASSIS

The air tube and drawer assembly are shipped in a carton separate from the burner
chassis. Choose the proper air tube length to obtain the tube insertion for the specific

installation.

A) Remove the AIR TUBE and BURNER CHASSIS from their respective cartons.

B) Remove the DRAWER ASSEMBLY (1) from inside the AIR TUBE by loosening the

screw (2). Carefully pull the DRAWER ASSEMBLY out of the AIR TUBE, instal the

required nozzle (see page 7) and set aside.

C) Remove the two BOLTS (3) from FRONT PLATE (4) of the BURNER CHASSIS.

Align the two holes on the AIR TUBE HOLDING PLATE (5) with the two holes left

open on the BURNER CHASSIS FRONT PLATE when the BOLTS (3) were removed.

Replace the BOLTS and finger tighten only. Re-install DRAWER ASSEMBLY into AIR

TUBE. Tighten SCREW (2) securely (see page 7).

D) Tighten the two bolts (3) securely.

MOUNTING THE BURNER

TO THE BOILER OR FURNACE

There are three possible methods to mount the burner, depending on the individual
application. These are:

1) Universal flange bolted to Boiler/Furnace unit.

2) Semi-flange collar bolted to Boiler/Furnace unit.

3)

Universal

flange

mounted

to

optional

Pedestal

mount,

where

flange-mounting

direct to appliance is not possible. Pedestal kit must be ordered separately.

METHOD 1 - UNIVERSAL MOUNTING FLANGE

A)

Insert the two BOLTS (1) into the UNIVERSAL MOUNTING FLANGE (10) from the

flat side, ensuring the bolt heads are flush with the flat surface. Secure in place using

two special CHROME NUTS (2) provided.