Appliance application requirements – Sears N8MPL050B12B1 User Manual

Page 17

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Exterior Masonry Chimney,

FAN+NAT Installations with

Type-B Double-Wall Vent Connectors

© NFPA & AG A

Table A-

Combined Appliance

Maximum Input Rating in

Thousands of Btu per Hr

VENT

HEIGHT

(FT)

INTERNAL AREA OF CHIMNEY

(SQ IN.)

12 19 28 38

6

74

119

178

257

8

80

130

193

279

10

84

138

207

299

15

NR

152

233

334

20

NR

NR

250

368

30

NR

NR

NR

404

Table B-

Minimum Allowable Input Rating of

Space-Heating Appliance in

Thousands of Btu per Hr

VENT

HEIGHT

(FT)

INTERNAL AREA OF CHIMNEY

(SQ IN.)

12 19 28

38

Local 99% Winter Design Temperature: 17 to 26° F*

6

0

55

99

141

Ü.

8

52

74

111

154

CM

0

10

NR

90

125

169

r*>^

15

NR

NR

167

212

20

NR

NR

212

258

30

NR

NR

NR

362

Local 99%

Winter Design Temperature: 5 to 16° F*

6

NR

78

121

166

Ü-

8

NR

94

135

182

CO

10

NR

111

149

198

15

NR

NR

193

247

20

NR

NR

NR

293

30

NR

NR

NR

377

Local 99% Winter Design Temperature: -

10 to 4° F*

6

NR

NR

145

196

Ü.

0

8

NR

NR

159

213

0

10

NR

NR

175

231

o

15

NR

NR

NR

283

20

NR

NR

NR

333

30

NR

NR

NR

NR

-11° F

Local 99%

Winter Design Temperature:

-11°F or

or

lower*

lower

Not recommended for any vent configuration

* The 99% Winter Design Dry-Bulb (db) temperatures are found in the

1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1

(United States) and 2 (Canada), or use the 99.6% heating db

temperaturesfound in the 1997 or 2001 ASHRAE Fundamentals

Handbook, Climatic Design Information chapter, Table 1A (United

States) and 2A (Canada).

Inspections before the sale and at the time of installation will deter­

mine the acceptability of the chimney or the need for repair and/or

(re)lining. Refer to the Chimney Inspection Chart to perform a

chimney inspection._______________________________________

If the inspection of a previously used tile-lined chimney:

a.

Shows signs of vent gas condensation, the chimney should

be relined in accordance with local codes and the authority

having jurisdiction. The chimney should be relined with a
listed metal liner, Type-B vent, or a listed chimney adapter
kit to reduce condensation. If a condensate drain is required

by local code, refer to the NFGC, Section 10.9 for additional

information on condensate drains.

b.

Indicates the chimney exceeds the maximum permissible

size in the tables, the chimney should be rebuilt or relined to
conform to the requirements of the equipment being
installed and the authority having Jurisdiction.

A chimney without a clay tile liner, which is otherwise in good con­
dition, shall be rebuiltto conform to ANSI/NFPA 211 or be lined with
a UL listed (ULC listed in Canada) metal liner or UL listed Type-B
vent. Relining with a listed metal liner or Type-B vent is consid­
ered to be a vent-in-a-chase.

If a metal liner or Type-B vent is used to line a chimney, no other

appliance shall be vented into the annular space between the
chimney and the metal liner.

APPLIANCE APPLICATION REQUIREMENTS

Appliance operation has a significant impact on the performance
of the venting system. If the appliances are sized, installed, ad­

justed, and operated properly, the venting system and/or the ap­

pliances should not suffer from condensation and corrosion. The

venting system and all appliances shall be installed in accordance

with applicable listings, standards, and codes.

The furnace should be sized to provide 100 percent of the design

heating load requirement plus any margin that occurs because of

furnace model size capacity increments. Heating load estimates
can be made using approved methods available from Air Condi­
tioning Contractors of America (Manual J); American Society of

Heating, Refrigerating, and Air-Conditioning Engineers; or other

approved engineering methods. Excessive oversizing of the fur­

nace could cause the furnace and/or vent to fail prematurely.

When a metal vent or metal liner is used, the vent or liner must be in
good condition and be installed in accordance with the vent or liner

manufacturer's instructions.

To prevent condensation in the furnace and vent system, the fol­

lowing precautions must be observed:

1.

The return-air temperature must beat least 60° F db except

for brief periods of time during warm-up from setback at no
lower than 55°F db or during initial start-up from a standby
condition.

2.

Adjust the gas input rate per the installation instructions.

Low gas input rate causes low vent gas temperatures, caus­

ing condensation and corrosion in the furnace and/or vent­
ing system. Derating is permitted only for altitudes above

2000

' .

3.

Adjust the air temperature rise to the midpoint of the rise

range or slightly above. Low air temperature rise can cause
low vent gas temperature and potential for condensation

problems.

4.

Set the thermostat heat anticipator or cycle rate to reduce

short cycling.

Air for combustion must not be contaminated by halogen com­

pounds which include chlorides, fluorides, bromides, and iodides.

These compounds are found in many common home products
such as detergent, paint, glue, aerosol spray, bleach, cleaning sol­
vent, salt, and air freshener, and can cause corrosion of furnaces
and vents. Avoid using such products in the combustion-air sup­

ply. Furnace use during construction of the building could cause

the furnace to be exposed to halogen compounds, causing prema­
ture failure of the furnace or venting system due to corrosion.

441 01 2613 02

R

t

I

Advertising