Natural gas input rating check, Orifice sizing, Warning – Sears N8MPL050B12B1 User Manual

Page 28: F28l

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

I

wise to decrease manifold pressure and clockwise to

increase pressure.

NOTE: Adjustment screw cover MUST be replaced on gas control

valve before reading manifold pressure and operating furnace.

4.

Set manifold pressure to value shown In Table 6 or Table 7.

5.

When the manifold pressure is properly set, replace the ad­

justment screw cover on the gas control valve.

Remove jumper wire from thermostat connection on fan

board. Remove manometer connection from manifold pres­

sure tap, and replace plug in gas valve.

Check for leaks at plug.

Operation Above 2000' Altitude

Natural Gas Input Rating Check

The gas meter can be used to measure input to furnace. Check
with gas supplier for actual BTU content.

1.

Turn OFF gas supply to all appliances other than furnace and
start furnace. Use jumper wire on R to W.

2.

Time how many seconds it takes the smallest dial on the gas
meter to make one complete revolution.

Note: If meter uses a 2 cubic foot dial, divide results (seconds) by

two.

Refer to Example. The Example is based on a natural gas BTU

content of 1,000 BTU's per cubic foot.

Example

Natural Gas

BTU Content

per cubic foot

No. of Seconds

Per Hour

Time Per Cubic

Foot in

Seconds

BTU Per

Hour

1,000

3,600

48

75,000

1,000 X 3,600^48 =

75,000 BTUH

3.

Remove jumper wire from R to W.

4.

Relight all appliances and ensure all pilots are operating.

Orifice Sizing

NOTE: Factory sized orifices for natural and LP gas are listed in

the furnace Technical Support Manual.

Ensure furnace is equipped with the correct main burner orifices.
Refer to Table 6 or Table 7 for correct orifice size and manifold

pressure for a given heating value and specific gravity for natural

and propane gas.

WARNING

FIRE, EXPLOSION,

POISONING HAZARD.

CARBON MONOXIDE

Failure to follow these instructions exactly could

result in death, personal injury and/or property dam­
age.

This high-altitude gas-conversion shall be done by

a qualified service agency in accordance with the
Manufacturer's instructions and all applicable

codes and requirements, or in the absence of local
codes, the applicable national codes.

These furnace may be used at full input rating when installed at al­
titudes up to 2000'. When installed above 2000', the input must be
decreased 2% (natural) or 4% (LP) for each 1000' above sea level
in the USA. In Canada, the input rating must be derated 5% (natu­
ral) or 10% (LP) for each 1000' above sea level. This may be ac­
complished by a simple adjustment of manifold pressure or an
orifice change, or a combination of a pressure adjustment and an
orifice change. The changes required depend on the installation
altitude and the heating value of the fuel. Table 6 & Table 7 show
the proper furnace manifold pressure and gas orifice size to
achieve proper performance based on elevation above sea level
for both natural gas and propane gas.

To use the natural gas table, first consult your local gas utility for

the heating value of the gas supply. Select the heating value in the

first column and follow across the table until the appropriate eleva­

tion for the installation is reached. The value in the box at the inter­

section of the altitude and heating value provides not only the
manifold pressure but also the orifice size. In the natural gas tables

the factoy-shipped orifice size is in bold (42). Other sizes must be

obtained from service parts.

High Altitude Input Rate =

Nameplate Sea Level Input Rate x (Multiplier) [USA]

Elevation

High Altitude Multiplier

Natural Gas

LP Gas

200Г - 3000'

0.95

0.90

300Г - 4000'

0.93

0.86

4001' - 5000'

0.91

0.82

5001' - 6000'

0.89

0.78

6001' - 7000'

0.87

0.74

7001' - 8000'

0.85

0.70

Based on mid-range of elevation.

f28l

441 01 2613 02