Heating request with gas shut off, Control board diagnostic codes (see figure 40) – Sears N8MPL050B12B1 User Manual

Page 34

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Heating Request with Gas Shut Off:

24 VAC signal applied to W terminal of FCB.
The FCB will attempt 4 cycles for ignition then go to soft lockout for 3 hours then try for ignition again as long as the heat call remains.

Power reset will clear lockout.

• Inducer motor turns on

• Following a 15 second prepurge delay, the igniter begins warm up.

• The igniter glows red-hot for 22 seconds, then turns off. The FCB flashes error code

6.

• The igniter stays off for 17 seconds, then begins to warm up

again.

• The igniter glows red hot for 22 seconds then turns off. The

FCB continues flashing error

code

6.

• The igniter stays off for 17 seconds, then begins to warm up

again.

• The igniter glows red hot for 22 seconds then turns off. The

FCB continues flashing error

code

6.

• The igniter stays off for 17 seconds, then begins to warm up

again.

• The igniter glows red hot for 22 seconds then turns off. The FCB proceeds to soft lockout and stops flashing error code

6 and begins

flashing error code

6 + 1.

• The inducer motor de-energizes after a 15 second post purge.

Control Board Diagnostic Codes (See Figure 40)

OFF

= 24VAC or 115VAC is off, fuse is open

Fleartbeat = Normal operation or no previous Diagnostic Code

ON SOLID = Soft Lockout - Furnace Control Error (1 hr delay)

If code repeats immediately following power reset then replace control

1 Flash

= Not used

2 Flashes

= Pressure switch(es) closed when should be open

3 Flashes

= Pressure switch open when should be closed

4 Flashes

= Limit or roll-out switch open (less than 2 minutes)

5 Flashes

= Flame sensed out of sequence

6 Flashes

= Failure to ignite or flame sense lost while running

6 + 1 Flashes = Soft Lockout - Max trials for ignition reached (3hr delay)
7 Flashes

= Soft Lockout - Limit or roll-out switch open longer

than 2 minutes (1 hr delay)

(roll-out switch requires manual reset)

8 Flashes = Permanent Lockout - Gas valve relay contact stuck closed or miswired gas valve (power reset only)

10 Flashes = Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions

* If status code recall is needed, briefly (2-3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored

status code. Do not remove power or blower door before initiating status code recall or code will be lost. Code is automatically cleared
after 72 hours or upon power reset.

Proper flame sense microamps: 0.7 microamps D.C. minimum, 2.0 - 4.0 microamps

nominal