Sub-base for Combustible Floors - Downflow Coil

Adapter Box

The subbase for combustible floors is required when a downflow
furnace, used with a downflow coil box, is set on combustible
flooring.

1.

Cut the opening in the floor according to the dimensions in

Table 5 because the base is equipped with locating tabs that
center the base over the opening.

The opening in the base is

1V4 "shorter and iVg " narrower

than the minimum required size of the opening in the floor.

This is done to maintain a T'clearance between the floor and

the plenum.

2.

Fabricate the plenum to the dimensions given in Table 5.

Note that the dimensions given are outside dimensions.

3.

Set the base over the opening in the floor, centering the open­

ing in the base over the opening in the floor. Fasten the base

to the floor with screws or nails. See Figure 29 and

Figure 30.

4.

Drop the plenum through the opening in the base. The flange

of the plenum should rest on top of the combustible floor base.

Figuro 29

Exploded View of Base for

Downflow Cased Coil

Figure 30

Setting the Base

Coil Box

Subbase

Insulation

Wood Screw-

Plenum

Floor

2S-20-46A

Consideration must be given to the height of the base to allow for

easy installation of the condensate drain. See Figure 31. This
subbase for combustible floors has been designed so that the

height of the subbase raises the downflow coil off the floor to allow

easy installation of the condensate drain

Figure 31

Condensate Line Raised by Base

25-20 52

Non-Combustible Floor

Set the furnace over the opening in the floor. If necessary, grout

around the base to seal air leaks between the base and the floor.

Duct Connections

In the downflow position, the return-air duct must be connected to

only the top of the furnace. Top return connections can be made by

removing the knockout panel in the furnace base. Return air con­
nection through the side(s) or back of the furnace is NOT allowed.