MANIFOLD PRESSURE AND ORIFICE SIZE FOR HIGH ALTITUDE APPLICATIONS

TablP 6

NATURAL GAS MANIFOLD PRESSURE (" w.c.)

MEAN ELEVATION FEET ABOVE SEA LEVEL

HEATING

0 to

2001 to

3001 to

4001 to

5001 to

6001 to

7001 to

VALUE

2000

3000

4000

5000

6000

7000

8000

at ALTITUDE

Orifice

Manifold

Orifice

Manifold

Orifice

Manifold

Orifice

Manifold

Orifice

Manifold

Orifice

Manifold

Orifice

Manifold

BTU/CU. FT.

No.

Pressure

No.

Pressure

No.

Pressure

No.

Pressure

No.

Pressure

No.

Pressure

No.

Pressure

700

41

3.7

725

1

3.7

41

3.4

750

1

3.5

42

3.6

775

-1

3.6

42

3.6

42

3.3

800

41

3.6

42

3.7

42

3.4

42

3.1

825

■:

1

J.

/

41

3.4

42

3.5

42

3.2

42

2.9

850

4|

3,5

42

3.6

42

3.3

42

3.0

42

2.8

875

:■

41

3.6

42

3.6

42

3.4

42

3.1

42

2.8

42

2.6

900

42

3.7

42

3,4

42

3.2

42

2.9

42

2.7

42

2.5

925

41

3.7

42

3.5

42

3.3

42

3.0

42

2.8

42

2.5

44

3.3

950

41

3.5

42

3.3

42

3.1

42

2.9

42

2.6

42

2.4

44

3.1

975

42

3.7

42

3.2

42

2.9

42

2.7

42

2.5

44

3.2

45

3.6

1000

42

3.5

42

3.0

42

2.8

42

2.6

42

2.4

45

3.7

45

3.4

1050

42

3.2

42

2.7

42

2.5

44

3.3

45

3.6

--

--

--

1100

43

3.6

42

2.5

44

3.2

45

3.6

NOTE; Natural gas data is based on 0.60 specific gravity.

Z223.1-2002/NFPA 54-2002 or National Standard of Canada,

For fuels with different specific gravity consult the National Fuel Gas Code ANSI

Natural Gas And Propane Installation Code CSA B149.1 -05.

Tcible 7

LPG or PROPANE GAS MANIFOLD PRESSURE (" w.c.)

HEATING VALUE

at ALTITUDE

BTU/CU. FT.

MEAN ELEVATION FEET ABOVE SEA LEVEL

0 to

2000

2001 to

3000

3001 to

4000

4001 to

5000

5001 to

6000

6001 to

7000

7001 to

8000

2500

10.0

10.0

9.0

10.0

9.4

8.5

10.0

Orifice Size

#54

#54

#54

#55

#55

#55

#56

NOTE; Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1 -2002/NFPA

54-2002 or National Standard Of Canada, Natural Gas And Propane Installation Code CSA B149.1 -05.

NOTE: The derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design-certified by CSA.
In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 above sea level. Use

the 2001 to 3000 column in Table

6 and Table 7.

The burner orifice part nos. are as follows:
Orifice #41

1096942

Orifice #42

1011351

Orifice #43

1011377

Orifice #44

1011352

Orifice #45

1011353

Orifice #54

1011376

Orifice #55

1011354

Orifice #56

1011355

High Altitude Air Pressure Switch

The factory-installed pressure switch need NOT be changed for
any furnace installations from sea level up to and including

8,000'

altitude

Changing Orifices

1.

After disconnecting power and gas supply to the furnace, re­

move the burner compartment door, exposing the burner
compartment.

2.

Disconnect gas line from gas valve so manifold can be re­

moved.

3.

Disconnect wiring at gas valve. Be sure to note the proper

location of all electrical wiring before being disconnected.

4.

Remove the four (4) screws holding the manifold and gas

valve to the manifold supports. Do not discard any screws.

See Figure 35._______________________________________

6.

Remove the orifices from the manifold and replace them with

proper sized orifices. See Figure 36.

7.

Tighten orifices so they are seated and gas-tight. See

Figure 36.

8.

Reassemble all parts in reverse order as removed. Be sure to

engage the main burner orifices in the proper openings in the

burners.

441 01 2613 02