Single dryer venting, Horizontal single dryer venting 8 inch ducting – American Dryer Corp. AD-385 User Manual

Page 18

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downweird

should be installed where the exhaust exits the building. If the duct work travels vertically up
through the roof, it should be protected from the weather by using a 180° turn to point the opening
downward. In either case, allow at least twice the diameter of the duct between the duct opening
and the nearest obstruction.

IMPORTANT: DO NOT use screens or caps on the outside of opening of exhaust duct

work.

IMPORTANT: Exhaust back pressure measured by a manometer at each basket

(tumbler) exhaust duct area

should not

exceed 0.3 inches of water column.

SINGLE DRYER VENTING

IMPORTANT: For exhaust duct runs of over 10 feet a minimum duct size of 10-inches

must be used.

When single 8-inch venting is used, the duct work from the dryer to the outside outlet cannot

exceed 10 feet (refer to Ulus. A below). This calculation of 10 feet compensates or allows for the use
of a maximum of only one (1) elbow (which is the outside outlet protection).

Ilus. A.

HORIZONTAL SINGLE DRYER

VENTING 8 INCH DUCTING

10 FEET MAXIMUM-

MAN1571

2x0

MOTE A: OPEMII^ ttlST BE ЛУ0 <21 INCHES LARGER THAN THE OUCT lALL THE WAY AROUND)

THE ШСТ MUST BE CENTERED WITHIN THIS OPENING.

14

Advertising