24

Operation Theory

Scan Timing and Procedure

There are four counters that need to be specified prior to program-
mable scans. Refer to Table 4-4 for details.

Counter Name Width

Description

Notes

SI_counter

24-bit

Scan Interval defines the
interval between each
scan.

Scan Interval =

SI_counter / Time-base*

SI2_counter

24-bit

Sampling Interval defines
the interval between each
sampled channel.

Sampling Interval =

SI2_counter / Timebase*

PSC_counter

24-bit

Post Scan Counts defines
how many scans to be
performed with respect to
each trigger.

Delay_counter 16-bit

Define the delay time for
scan after trigger.

Delay Time =

(Delay_counter / Time-

base*), Timebase*=40M

for DAQ/DAQe/PXI-2502/

2501

Table 4-4: Summary of Counters for Programmable Scan